Sentry 5000-32-IT Controller
Page 54 of 82
describes alarm state logic behavior on TPC display
, Front Panel LED’s and Alarm Relays.
Condition
Result
Configuration
Status
Screen
LED
Relay
Alarm condition with Latch
configuration
Alarm
Flash
Flash
On
Reset* Solid
Solid
On
Alarm Clears
-
-
Off
Condition clears
before Reset
Alarm
Flash
Flash
On
Alarm Clears
Flash
Flash
On
Reset* -
-
Off
Alarm condition with Non-
Latch configuration
Alarm
Flash
Flash
On
Reset* Solid
Solid
On
Alarm Clears
-
-
Off
Condition clears
before Reset
Alarm
Flash
Flash
On
Alarm Clears
-
-
Off
Alarm condition with Alarm
Acknowledge configuration
Alarm
Flash
Flash
On
Reset* Solid
Solid
Off
Alarm Clears
-
-
Off
Condition clears
before Reset (Ackn.)
Alarm
Flash
Flash
On
Alarm Clears
Flash
Flash
On
Reset* -
-
Off
Warning condition with Latch
configuration
Warning
Solid
Solid
On
Reset* Solid
Solid
On
Warning Clears
-
-
Off
Condition clears
before Reset
Warning
Solid
Solid
On
Warning Clears
Solid
Solid
On
Reset* -
-
Off
Warning condition with Non-
Latch configuration
Warning
Solid
Solid
On
Reset* Solid
Solid
On
Warning Clears
-
-
Off
Condition clears
before Reset
Warning
Solid
Solid
On
Warning Clears
-
-
Off
Warning condition with
Acknowledge configuration
Warning
Solid
Solid
On
Reset* Solid
Solid
Off
Warning Clears
-
-
Off
Condition clears
before Reset
Warning
Solid
Solid
On
Warning Clears
Solid
Solid
On
Reset* -
-
Off
Figure 33: Alarm Conditions
* Reset is Input by TPC display menu, integral switch, remote switch, or Modbus command.
Summary of Contents for Sentry 5000-32-IT
Page 28: ...Sentry 5000 32 IT Controller Page 28 of 82 Figure 15 Analog Input Wiring ...
Page 29: ...Sentry 5000 32 IT Controller Page 29 of 82 Figure 16 PSG Sentry Classic Wiring ...
Page 30: ...Sentry 5000 32 IT Controller Page 30 of 82 Figure 17 Modbus Wiring ...
Page 31: ...Sentry 5000 32 IT Controller Page 31 of 82 Figure 18 Top Board Relay Digital Output Wiring ...
Page 32: ...Sentry 5000 32 IT Controller Page 32 of 82 Figure 19 Analog Output Wiring ...
Page 33: ...Sentry 5000 32 IT Controller Page 33 of 82 Figure 20 Digital Input Wiring ...
Page 34: ...Sentry 5000 32 IT Controller Page 34 of 82 Figure 21 Bottom Board Relay Wiring ...