Sentry 5000-32-IT Controller
Page 37 of 82
5.4
Configure Modules
The process to configure the discovered modules is dependent upon the method of communication
between the controller and the modules. If the controller was set up in the factory discovered modules will
default to factory configured parameters.
5.4.1 Modbus
Modbus communication will discover all the important sensor module values and load them from the
module into the controller memory.
5.4.2 Analog
Analog communication only discovers the input on the Analog Input stack connection. All required module
parameters must be manually input via the TPC display.
5.4.3 PSG
PSG communication loads a small subset of parameters from the module to the controller. The remaining
parameters must be manually configured via the Set-Module Screen and Sensor Setup Form.
Parameter
Modbus
Analog 4-20 mA
PSG
Note
Sensor Address
Auto Discover by loop
number and module
rotary switch
Auto Discover by stack
number and channel
number
Auto Discover by stack
number, loop number
and module rotary
switch
Refer to
Module Type
Auto-discover
Combustible, Toxic or
Oxygen
Manual input
Auto-discover
Combustible, Toxic or
Oxygen
Gas Tag
Manual pull down list
Alarm Level
Auto Discover
Manual Input
Latch
Auto Discover
Manual Input
Warning Level
Auto Discover
Manual Input
Latch
Auto Discover
Manual Input
Calibration Gas
Default based on Gas Tag
– Pull down list for manual update
Calibration Interval
Default based on Gas Tag
– Pull down list for manual update
Calibration Span
Default based on Gas Tag
– Pull down list for manual update
Module Tag
Default is the Sensor Address
– Manual input for custom tag
Module Number
Manual Input
Units
Auto update based on Module Type
Figure 24: Data Detail by Communications Method
Summary of Contents for Sentry 5000-32-IT
Page 28: ...Sentry 5000 32 IT Controller Page 28 of 82 Figure 15 Analog Input Wiring ...
Page 29: ...Sentry 5000 32 IT Controller Page 29 of 82 Figure 16 PSG Sentry Classic Wiring ...
Page 30: ...Sentry 5000 32 IT Controller Page 30 of 82 Figure 17 Modbus Wiring ...
Page 31: ...Sentry 5000 32 IT Controller Page 31 of 82 Figure 18 Top Board Relay Digital Output Wiring ...
Page 32: ...Sentry 5000 32 IT Controller Page 32 of 82 Figure 19 Analog Output Wiring ...
Page 33: ...Sentry 5000 32 IT Controller Page 33 of 82 Figure 20 Digital Input Wiring ...
Page 34: ...Sentry 5000 32 IT Controller Page 34 of 82 Figure 21 Bottom Board Relay Wiring ...