-53-
No.PF
※※
-OMM0005-N
■
[F30] Storing of accumulated flow
The default setting is not to store the accumulated flow when the power supply is turned off.
This function enables the accumulated flow value to be stored in permanent memory every 2 or 5 minutes.
The maximum writable limit of the memory device is 1 million cycles, which should be taken into
consideration.
If the product is operated 24 hours per day, the maximum writable limit will be as follows:
Data memorized every 5 minutes --- 5 minutes x 1 million cycles = 5 million minutes = 9.5 years
Data memorized every 2 minutes --- 2 minutes x 1 million cycles = 2 million minutes = 3.8 years
<Operation>
Press the
or
button in function selection mode to display [F30] on the main screen.
The sub screen displays [SAVE] and the current set value alternately.
Press the
button.
Sub screen
Press the
or
button to select the setting for storing accumulated
flow.
Press the
button to confirm.
Return to the function selection mode.
[F30] Setting of accumulated flow storing function is completed.
: Data memorization is performed every 2 or 5 minutes (depending upon the setting chosen), this means that the accumulated flow
value for up to 2 or 5 minutes before the power supply is turned off will not be added to the device memory.
When the power supply is turned on again, the accumulated flow count will start from the value recorded
at B.
Summary of Contents for PF3W7 Series
Page 12: ...11 No PF OMM0005 N Model Indication and How to Order Metal piping...
Page 13: ...12 No PF OMM0005 N Polyvinyl chloride piping...
Page 45: ...44 No PF OMM0005 N List of output modes for fluid temperature...
Page 48: ...47 No PF OMM0005 N Example of display of sub screen...
Page 49: ...48 No PF OMM0005 N Example of display of sub screen continued...
Page 78: ...77 No PF OMM0005 N PF3W711 Vinyl chloride piping PF3W721 Vinyl chloride piping...