Error indication function
This function is to display error location and content when a problem or an error occurs.
Error Name
Error Display
Error Type
Troubleshooting Method
Over current
Error
A load current of switch output is 80 mA or
more.
Turn the power off and remove the
output factor for the over current.
Then turn the power on.
Residual
Pressure Error
During zero clear operation, pressure over
±10% of the span between atmospheric
pressure and upper limit of rated pressure
is applied. After 1 s, the mode will reset to
the measurement mode. ±1 digit of the zero
clear range varies with individual product
differences.
Perform zero clear operation again
after restoring the applied pressure
to an atmospheric pressure
condition.
Pressure has exceeded the upper limit of
the set pressure range.
Pressurizing
Error
Pressure has exceeded the lower limit of
the set pressure range.
Reset applied pressure to a level
within the set pressure range.
Auto-shift Error
The measured pressure at auto-shift input
exceeds the set pressure range.
∗
: After 1 s, measurement mode returns
automatically.
Auto-shift input is invalid by
connected equipment and machine.
Check the connected equipment
and machine.
System Error
Displayed in the case of an internal data
error.
Turn the power off and turn it on
again.
If resetting fails, an investigation by
SMC Corporation will be required.
If the error can not be reset after the above measures are taken, then please contact SMC.
Summary of Contents for ISE80(H)
Page 17: ...16 PS OMM0003 A Mounting with panel mount adapter Rear piping Bottom piping...
Page 55: ...54 PS OMM0003 A Dimensions Z ISE80 02 Z ISE80 02L...
Page 56: ...55 PS OMM0003 A Z ISE80 N02 Z ISE80 N02L...
Page 57: ...56 PS OMM0003 A Z ISE80 F02 Z ISE80 C01...
Page 58: ...57 PS OMM0003 A Z ISE80 C01L Z ISE80 A2...
Page 59: ...58 PS OMM0003 A Z ISE80 A2L Z ISE80 B2...
Page 60: ...59 PS OMM0003 A Z ISE80 B2L...