-19-
PS##-OMM0003-A
■
Wiring
○
Connection
•
Connections should only be made with the power supply turned off.
•
Use separate routes for the Pressure switch wiring and any power or high voltage wiring. Otherwise,
malfunction may result due to noise.
•
Ensure that the FG terminal is connected to ground when using a commercially available switch-mode
power supply. When a switch-mode power supply is connected to the product, switching noise will be
superimposed and the product specification can no longer be met. This can be prevented by inserting a
noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the
product, or by using a series power supply instead of a switch-mode power supply.
○
Internal circuit and wiring example
-N
NPN open collector output type
Max. 28 V, 80 mA
Residual voltage 1 V or less
-P
PNP open collector output type
Max. 80 mA
Residual voltage 1 V or less
-S/-R
(Analog output mode)
Switch output
NPN open collector output type 2 output
Max. 28 V, 8 mA
Residual voltage 1 V or less
R: Analog output 1 to 5 V
Output impedance 1 k
Ω
S: Analog output 4 to 20 mA
Max. load impedance
Power supply voltage 12 V: 300
Ω
Power supply voltage 24 V: 600
Ω
Min. load impedance 50
Ω
-S/-R
(Auto-shift input mode)
With auto-shift switch output
NPN open collector output type 2 output
Max. 28 V, 80 mA
Residual voltage 1 V or less
Summary of Contents for ISE80(H)
Page 17: ...16 PS OMM0003 A Mounting with panel mount adapter Rear piping Bottom piping...
Page 55: ...54 PS OMM0003 A Dimensions Z ISE80 02 Z ISE80 02L...
Page 56: ...55 PS OMM0003 A Z ISE80 N02 Z ISE80 N02L...
Page 57: ...56 PS OMM0003 A Z ISE80 F02 Z ISE80 C01...
Page 58: ...57 PS OMM0003 A Z ISE80 C01L Z ISE80 A2...
Page 59: ...58 PS OMM0003 A Z ISE80 A2L Z ISE80 B2...
Page 60: ...59 PS OMM0003 A Z ISE80 B2L...