IDX-OM-V020
Chapter 12
Option T
12.3
Remote operation
IDFA60/70/80/90 Series
12-2
12.3 Remote operation
230 VAC is applied to the terminal for remote operation. Select the appropriate switch.
- For remote operation, customer operates the switch which is connected by customer with the switch
with lamp ON.
- Position holding switch (alternate type switch).
Keep the jumper wire (terminal No. 4-5) connected for the remote terminal A.
Disconnect the jumper wire from the remote terminal B (terminal number 6-7) and connect the switch.
- Automatic return switch (momentary switch).
Disconnect the jumper wire from the remote terminal A (terminal number 4-5) and connect the switch (A
contact: operation signal), and then disconnect the jumper wire from the remote terminal B (terminal
number 6-7) and connect the switch (B contact: stop signal).
- Allow at least 3 minutes before restarting the dryer. If the air dryer is restarted within 3 minutes after
been stopped, the protection circuit will be activated.
In order to avoid motor failure, start-stop frequency of the product must be 5 times/ hour or less.
【
Restart the operation
】
- Error signal output is released by turning off the switch with lamp or giving an operation stop signal
remotely. Eliminate the cause of error. Restart operation after 3 minutes passed.
- When the error signal is not released even by turning off the switch with lamp, the thermal relay or high
pressure switch is activated. Reset the thermal relay or high pressure switch referring to 6.2 Reset the
Thermal relay and High Pressure Switch.