IDX-OM-V020
Chapter 11
Option R
11.3
Connection of power supply
IDFA60/70/80/90 Series
11-2
11.3 Connection of power supply
Connect the power cable according to the procedure below.
1) Remove the front panels.
2) Introduce the cable through the strain relief to connect to the terminal block. (refer to the label on
the terminal block)
M3.5
Screw tightening torque : 1.0 to 1.3N
・
m
M4.0
Screw tightening torque : 1.4 to 2.0N
・
m
Do not touch any equipment other than the terminal block during wiring.
3) Mount the front panel back.
Strain relief
Power supply cable entry
[Earth leakage breaker]
Test button (gray)
Leakage display button (white)
[Terminal block]
L N
※
Refer to the Chapter 3.2.5 Electrical wiring for
power cable connection.
Terminal block
Front panel
Earth leakage breaker