IDX-OM-V020
Chapter 7
Documents
7.2
Refrigerant and GWP value
IDFA60/70/80/90 Series
7-2
Note 1: The operating range does not guarantee use with normal air flow capacity.
Note 2: ANR indicates the following set of conditions: a temperature of 20°C, atmospheric pressure, and a
relative humidity of 65%.
Note 3: Air flow capacity converted by the compressor intake condition [32°C, atmospheric pressure, and
75% relative humidity].
Note 4: Do not use this product with continuous voltage fluctuations.
Note 5: These values are reference values under rated conditions and are not guaranteed. Do not use
these values for the thermal set values, etc.
Note 6: Products other than Option R are not equipped with an earth leakage breaker. Purchase an
appropriate earth leakage breaker separately. Use an earth leakage breaker with a leak current
sensitivity of 30mA.
Note 7: This is the value specified by IPCC4 AR4. The value specified by
“Class 1 Act on Rational Use and
Proper Management of Fluorocarbons JAPAN
” is R410A GWP: 2090.
Note 8: The maximum operating pressure is 1.0MPa as standard, but it is possible to achieve 1.6MP when
selecting Option L or Option V.
Coefficient factors
Inlet air temperature (
o
C)
5 to 25
30
35
40
45
50
55
60
65
1.42
1.15
1.00
0.71
0.62
0.50
0.40
0.33
0.21
Inlet air pressure (MPa)
0.3
0.4
0.5
0.6
0.7 to 1.6
0.71
0.75
0.82
0.89
1.00
Ambient temperature (
o
C)
2 to 25
30
35
40
45
1.0
0.85
0.80
0.73
0.62
Calculation example: The air flow capacity when the dew point of IDFA60 is set to 10
o
C under the
following conditions
< Operating conditions:
Inlet air temp: 35
o
C, Inlet air pressure: 0.6MPa, Ambient temp: 35
o
C
>
360 m
3
/h(ANR) ×1.00 × 0.89 × 0.80
=
256 m
3
/h(ANR)
7.2 Refrigerant and GWP value
Refrigerant
Global Warming Potential (GWP)
Regulation (EU) No 517/2014
(Based on the IPCC AR4)
Revised Fluorocarbons Recovery
and Destruction Law
(Japanese law)
R410A
2,088
2,090
Note 1: This product is hermetically sealed and contains fluorinated greenhouse gases (HFC).