3-7
3.3.3
Wiring installation
Power cable
The power cables are to be prepared under your responsibility, referring to the
following table.
Table 3-1 Power Cable and Main Breaker (This System)
Item
Type
Po
wer
c
a
b
le
Size (recommended)
10AWG
4-conductor
Crimp contact
(recommended)
Breaker
R5.5-8
Earth bar
R5.5-8
Torque
(recommended)
Breaker
1
2.5N•m (1.84 ft-lbf)
Earth bar
12.5N•m (9.22 ft-lbf)
Main breaker (This System)
30A
Communication connector
The communication connectors are to be prepared under your responsibility,
referring to the following table.
Table 3-2 Communication Connector
Connector
Type (for your system)
Contact signal (P1 connector)
D-Sub 25-pin (male)
Serial RS-485 (P2 connector)
D-Sub 9-pin (male)
Only designated personnel are allowed to install wiring.
Be sure to turn OFF the power prior to wiring to assure safety.
Do not do any wiring when the system is energized.
The system wiring requires not only a thorough connection with the
designated cable but also securing to prevent loose connection. Poor
connection and securing may cause electric shock, heat sports, fire or
communication errors.
Be sure to supply the power to this system according to specifications.
Supply pure AC power. Potential malfunction may occur if a rectified AC
with voltage rise (dv/dt)
at zero crossing exceeds 40V /200µ sec.
Always establish a connection to a ground for safety.
Be sure that no ground connection is made to
a water pipe, gas pipe and lighting rod.
V
dV
dt
dt
= Voltage ratio
on zero-cross point
dV
t
Voltage rise %
Time
Voltage
Summary of Contents for HRW002-H
Page 6: ...HRX OM K003 Table of Contents HRW Series TOC 4...
Page 22: ...HRX OM K003 Chapter 1 Safety 1 8 Material Safety Data Sheet MSDS HRW Series 1 16...
Page 24: ...HRX OM K003 Chapter 2 Name of Each Section 2 1 Name of Each Section HRW Series 2 2...
Page 60: ...HRX OM K003 Chapter 5 System Operation 5 4 Examples of System Operation HRW Series 5 16...
Page 64: ...HRX OM K003 Chapter 6 Error Message and Troubleshooting 6 2 Troubleshooting HRW Series 6 4...
Page 86: ......