HRX-OM-K003
Chapter 8 Appendix
HRW Series
8.4 Offset Function
8-11
When MODE2 is selected
With OFFSET value set at -1°C, TEMP PV and communication data express
“29°C” (circulating fluid discharge temp. value + OFFSET value) that agrees with
the temperature of the circulating fluid in your system.
Figure 8-6 When MODE2 is selected
When MODE3 is selected
This mode enables this system to exercise temperature control to obtain 31°C
(TEMP SP value +OFFSET value), with OFFSET value set at 1°C. Once the
discharge temperature of the circulating fluid becomes 31°C, 1°C-thermal
dissipation is assured to allow the circulating fluid in your system to be 30°C.
TEMP SP value is obtained for your system. TEMP PV and communication data
also express “30°C” (circulating fluid discharge temp. value - OFFSET value) that
agrees with the temperature of the circulating fluid in your system.
Figure 8-7 When MODE3 is selected
1°C
This system
Your system
Discharge temp.:
30°C
Circulating fluid temp. in
your system: 29°C
TEMP PV 29°C
TEMP SP 30°C
OFFSET -1°C
External communication
Communication data
TEMP PV 29°C
TEMP PV
29°C
Heat dissipation:
Heat
1°C
This system
Your system
Discharge temp:
31°C
Circulating fluid temp. in
your system: 30°C
TEMP PV 30°C
TEMP SP 30°C
OFFSET 1°C
External communication
Communication data
TEMP PV 30°C
TEMP PV
30°C
dissipation:
Summary of Contents for HRW002-H
Page 6: ...HRX OM K003 Table of Contents HRW Series TOC 4...
Page 22: ...HRX OM K003 Chapter 1 Safety 1 8 Material Safety Data Sheet MSDS HRW Series 1 16...
Page 24: ...HRX OM K003 Chapter 2 Name of Each Section 2 1 Name of Each Section HRW Series 2 2...
Page 60: ...HRX OM K003 Chapter 5 System Operation 5 4 Examples of System Operation HRW Series 5 16...
Page 64: ...HRX OM K003 Chapter 6 Error Message and Troubleshooting 6 2 Troubleshooting HRW Series 6 4...
Page 86: ......