Chapter 6 Error Message and Troubleshooting
6.2 Troubleshooting
HRW Series
6-2
6.2 Troubleshooting
The procedure for error recovery varies with alarm types.
Alarm Code.01 to 08, 10 to 19, 22, 24, 29, 30:
Eliminate the error cause. Press the [RESET] key on the operation display panel
or power cycle the main breaker to enable error recovery to take effect.
Alarm Code.09:
Eliminate the error cause. After replacing thermal fuse, press the [RESET] key
on the operation display panel or power cycle the main breaker to enable error
recovery to take effect.
Alarm Code.21:
Eliminate the error cause, and power cycle the main breaker to enable error
recovery to take effect.
Alarm Code.23, 26, 27:
Automatic error recovery is implemented upon elimination of the error.
Alarm Code.18, 24, 26, 27:
This is an alarm for accessories (optional). No alarm of this type is issued if the
system is outfitted with no accessories.
Alarm Code.25:
This alarm is only for HRW
-
H
S (pump inverter type).
Table 6-1 Troubleshooting (1/2)
Code
Error message
System
condition
Cause
Remedies
01
Water Leak
Detect FLT
Stop
The fluid is pooled at the base
of this system.
Check for fluid leak.
02
Incorrect Phase
Error FLT
Stop
The power phase rotation is
wrong.
Check that a proper connection
is established between the
power cable and main breaker
of this system.
05
Reservoir Low
Level FLT
Stop
An insufficient amount of the
circulating fluid is observed in
the tank.
Replenish the circulating fluid.
06
Reservoir Low
Level WRN
Continued
An insufficient amount of the
circulating fluid is observed in
the tank.
Replenish the circulating fluid.
07
Reservoir High
Level WRN
Continued
An excessive amount of the
circulating fluid is observed in
the tank.
Drain the circulating fluid.
08
Temp. Fuse
Cutout FLT
Stop
The circulating fluid tank was
raised in temperature.
Check the load specification.
Replacement of the thermal
fuse is required.
Call the supplier for service.
09
Reservoir High
Temp. FLT
Stop
The temperature of the
circulating fluid exceeded the
specified value.
Check the load specification.
10
Return High
Temp. WRN
Continued
The
temperature
of
the
circulating fluid exceeded the
specified value.
Check the circulating fluid flow
rate and load specification.
11
Reservoir High
Temp. WRN
Continued
The temperature of the
circulating fluid exceeded
your specified value.
Reset the setting temperature.
Summary of Contents for HRW002-H
Page 6: ...HRX OM K003 Table of Contents HRW Series TOC 4...
Page 22: ...HRX OM K003 Chapter 1 Safety 1 8 Material Safety Data Sheet MSDS HRW Series 1 16...
Page 24: ...HRX OM K003 Chapter 2 Name of Each Section 2 1 Name of Each Section HRW Series 2 2...
Page 60: ...HRX OM K003 Chapter 5 System Operation 5 4 Examples of System Operation HRW Series 5 16...
Page 64: ...HRX OM K003 Chapter 6 Error Message and Troubleshooting 6 2 Troubleshooting HRW Series 6 4...
Page 86: ......