HRX-OM-K003
Chapter 1 Safety
HRW Series
1.5 Safety Measures
1-11
Lockout procedure
1.
T
urn the breaker handle to ‘OFF
’.
2.
Turn the breaker handle to ‘RESET’.
Hold the breaker handle with hand.
The handle turns back to ‘OFF
’ if released.
3.
Pull the lock mounting part out of the
breaker handle, and turn the breaker
handle to ‘OFF
’.
The lock mounting part is to remain pulled
out.
4.
Lock the lock mounting part with the
padlock.
Releasing lockout
1.
Remove the padlock from the lock mounting part.
2.
Turn the
breaker handle to ‘RESET’.
The lock mounting part is pulled in.
The handle turns back to ‘OFF
’ if released.
Figure 1-11
Breaker Handle at ‘OFF
’
Figure 1-12
Breaker Handle at ‘RESET’
Figure 1-13 Pulling-out of Lock Mounting Part
Figure 1-14 Breaker Lock
Padlock
Lock mounting part
Lock
mounting
part
All service personnel must observe the restrictions applied during
lockout and are required to perform lockout in accordance with this
procedure. No service personnel is allowed to start, energize, or use
the locked out system.
Summary of Contents for HRW002-H
Page 6: ...HRX OM K003 Table of Contents HRW Series TOC 4...
Page 22: ...HRX OM K003 Chapter 1 Safety 1 8 Material Safety Data Sheet MSDS HRW Series 1 16...
Page 24: ...HRX OM K003 Chapter 2 Name of Each Section 2 1 Name of Each Section HRW Series 2 2...
Page 60: ...HRX OM K003 Chapter 5 System Operation 5 4 Examples of System Operation HRW Series 5 16...
Page 64: ...HRX OM K003 Chapter 6 Error Message and Troubleshooting 6 2 Troubleshooting HRW Series 6 4...
Page 86: ......