Fig. 2 Front Panel
Table 6 Indicator Description
Indicator
Indicator Description
S1 Power Status
Indicator
Lamp On: S1 Power normal;
Lamp Flashing: S1 Power abnormal (under/over voltage, under/over
frequency, loss of phase, reverse phase sequence);
Lamp Off: S1 Power none voltage;
S1 Close Status
Indicator
Lamp On: S1 close auxiliary status input is active;
S2 Power Status
Indicator
Lamp On: S2 Power normal;
Lamp Flashing: S2 Power abnormal (under/over voltage, under/over
frequency, loss of phase, reverse phase sequence);
Lamp Off: S2 Power none voltage;
S2 Close Status
Indicator
Lamp On: S2 close auxiliary status input is active;
Alarm Indicator
Lamp Slow Flashing: flashes when warning alarm occurs (1 time for 1
second);
Lamp Fast Flashing: flashes when fault alarm occurs (5 times for 1
second);
Load Live Indicator
Lamp On: When load voltage monitoring is enabled, load end voltage is up
to rated 70%; When it is not enabled, S1 close signal input is active, or S2
close signal input is active. (Default: load voltage monitoring disabled.)
Auto Trans./Auto Res.
Lamp On: Current status is Auto Transfer/Auto Restore.
Auto Trans./Non-Res.
Lamp On: Current status is Auto Transfer/Non Restore.
Manual Mode Indicator
Lamp On: Current mode is Manual mode.
Auto Mode Indicator
Lamp On: Current mode is Auto mode.