background image

                                         

 

HAT600P Series ATS Controller User Manual                                                                              Page 42 of 58

 

14.3

 

SYNCHRONIZING CLOSE 

Synchronizing close is transferring current power side to the other power supply under normal condition 
of both S1 and S2. During this process synchronizing transfer is needed.   

Parallel  Mode

:  When  select  parallel  mode  and  the  corresponding  functions  of  input  port,  sync  close 

function is active, when select non-parallel mode, sync. close function cannot be executed.   

Sync. Volt Difference

: Maximum volt difference between S1 and S2 at synchronization; if it is enabled, 

volt difference won't be detected in synchronizing process.   

Sync. Freq. Difference

: Maximum frequency difference between S1 and S2 at synchronization.   

Sync.  Phase  Difference

:  Maximum  phase  difference  between  S1  and  S2  at  synchronization.  Usually 

phase difference shall not be set too big. Otherwise, load impact will be too big at closing.   

Fail To Sync Action

: Warning alarm or fault alarm can be set; after sync failure, it continues waiting for 

sync until sync close is finished. For warning alarm when sync is completed or it exits from sync, alarm 
shall be cleared; for fault alarm, it needs alarm reset key to clear the alarm. 

Transfer On Sync Fail

: When this is enabled, after sync fails, non sync close will be conducted and no 

sync failure alarm shall be issued.     

Fail To Sync Delay

: Waiting time for sync; it shall issue sync failure alarm when it is overtime.   

Breaker Feedback Time

: Pulse time for synchronizing close; at the time of synchronizing transfer, sync 

close/open output delay starts; in the delay process if correct close status is detected, then stop the 
close/open pulse output; if after delay is over, correct close status still cannot be detected, close/open 
failure alarm shall be initiated.   

 

Fig. 6 Sync Transfer Diagram 

Summary of Contents for HAT600P Series

Page 1: ...HAT600P SERIES HAT600P HAT600PB HAT600PI HAT600PBI HAT600PS ATS CONTROLLER USER MANUAL...

Page 2: ...ct names used within this publication is owned by their respective companies SmartGen Technology reserves the right to change the contents of this document without prior notice Table 1 Software Versio...

Page 3: ...e 2 Symbol Illustration Symbol Illustration NOTE Implies or indicate operator to operate rightly CAUTION Indicates wrong operation may lead to impair apparatus HAZARD Indicates wrong operation may lea...

Page 4: ...ETS 21 8 2 3 SCHEDULED GEN START 22 8 2 4 SCHEDULE NOT WORK 22 9 PARAMETER SETTINGS 23 9 1 ILLUSTRATION 23 9 2 PARAMETER CONFIGURATION LIST 23 9 3 DIGITAL INPUT PORT FUNCTION DESCRIPTION 31 9 4 DIGITA...

Page 5: ...ATION CONFIGURATION 47 17 1 ILLUSTRATION 47 17 2 RS485 COMMUNICATION PORT 47 17 3 USB COMMUNICATION PORT 47 17 4 ETHERNET COMMUNICATION PORT 47 18 TERMINAL DESCRIPTION 48 18 1 CONTROLLER TERMINAL DESC...

Page 6: ...etect 2 way 3 phase voltage make accurate judgment and output passive control switch for occurred abnormal voltages over under voltage loss of phase over under frequency This controller is applicable...

Page 7: ...T600PI HAT600PBI HAT600PS DC Supply AC Supply LN90V 305V Current Monitor Synch Transfer Input Port No Fixed Flexible 2 4 2 4 2 4 2 4 2 4 Output Port No Fixed Flexible 2 6 2 6 2 6 2 6 2 6 Genset Contro...

Page 8: ...al mode With local mode the controller only displays data parameter when it is active and the switch needs to be transferred by external operations Electrical interlock release function for switching...

Page 9: ...Power Consumption 4W Standby mode 2W AC Voltage Input PT or PT Secondary is not used AC system HAT600P HAT600PI HAT600PB HAT600PBI HAT600PS 3P4W L L 80 625 V 80 528 V 80 520 V UL certification 3P3W L...

Page 10: ...ensions 198mmx154mmx54mm Panel Cutout 186mm x 141mm Operating Conditions Temperature 25 70 C Humidity 20 93 RH Temperature 55 C UL certification Storage Condition Temperature 30 80 C Protection Rank F...

Page 11: ...t Power kVA Load 3 Phase Power Facor PF Load Average Power Factor PF Voltage Difference of S1 and S2 Frequency Difference of S1 and S2 Phase Difference of S1 and S2 Continuous Power Supply Time Contin...

Page 12: ...se phase sequence Lamp Off S2 Power none voltage S2 Close Status Indicator Lamp On S2 close auxiliary status input is active Alarm Indicator Lamp Slow Flashing flashes when warning alarm occurs 1 time...

Page 13: ...e press to scroll up screen After entering menu page move up cursor or increase the value where the cursor is Press longer and it can mute alarms Set Confirm Key In main page press to enter menu page...

Page 14: ...ce the difference of average value of 3 phase voltages Synchronous Frequency Difference Synchronous Phase Difference and Analogue Synchronous Meter Current page content and position alarm status indic...

Page 15: ...us indication information and action countdown S1 Voltage Status S2 Voltage Status Switch Status Genset Status Current page content and position alarm status indication information and action countdow...

Page 16: ...Power value is within the specified range 4 S2 Voltage None Voltage is 0 5 S2 Voltage High Voltage is above the pre set upper value 6 S2 Voltage Low Voltage is below the pre set lower value 7 S2 Frequ...

Page 17: ...gets ready PF is active before S2 closes 16 Elevator Delay Delay time before switch transfer elevator control outputs 17 S1 On Load S1 was already closed and S1 is taking load 18 S2 On Load S2 was alr...

Page 18: ...11 Sync Fail Fault Sync failure action is set to fault when it is over delay time fault alarms 12 S1 S2 Close At the same time It alarms when S1 close signal input and S2 close signal input are active...

Page 19: ...starts when mains is abnormal 11 Genset Start Active when genset starts 12 Auto Mode Current status is Auto mode 13 Manual Mode Current status is Manual mode 14 Local Mode Current status is Local Mod...

Page 20: ...et start stop menu interface is as below 1 Return 2 S1 Genset Stop 3 S1 Genset Start 4 S2 Genset Stop 5 S2 Genset Start Press Up Down key to select different parameter line backlight and press Confirm...

Page 21: ...tification countdown is initiated Before the end of fault identification countdown if S1 generating is normal S1 takes the load as soon as it is normal After the end of S1 cycle running countdown S2 s...

Page 22: ...time is up When scheduled start lasting time is over start signal is disconnected Scheduled Run On Load or Off Load can be set Scheduled Start On Load genset start outputs and when generating is OK g...

Page 23: ...l to abnormal 5 Master Slave Set 0 1 0 0 S1 Master 1 S2 Master 6 System Type Set 0 3 0 0 S1 Mains S2 Gen 1 S1 Gen S2 Mains 2 S1 Mains S2 Mains 3 S1 Gen S2 Gen 7 AC System 0 3 0 0 3 Phase 4 Wire 1 3 Ph...

Page 24: ...is the set time Enable close open pulse output time is the set close open time 2 Close Time 0 1 20 0 s 5 0 Outputted pulse time of close relay 3 Open Time 0 1 20 0 s 5 0 Outputted pulse time of open...

Page 25: ...se Diff 0 20 5 Max phase difference when sync is completed 18 Fail to Sync Action 0 1 0 0 Warn Alarm 1 Fault Alarm It continues to wait for sync when sync fails until it closes after sync For warning...

Page 26: ...Disable 1 Enable 8 Battery Under Volt Warn Enable 0 1 0 0 Disable 1 Enable 9 Battery Under Volt Warn 0 100 0 V 10 0 It occurs when battery voltage is lower than the set value 10 Battery Under Volt Ret...

Page 27: ...January Bit1 February Bit2 March Bit3 April Bit4 May Bit5 June Bit6 July Bit7 August Bit8 September Bit9 October Bit10 November Bit11 December 13 Inhibit Date 1 31 1 Date of not start in every month 1...

Page 28: ...3600 s 5 18 NEL Over Power Val 2 0 200 100 When load power is over the set value unload control outputs after delay 19 NEL Over Power Delay 2 0 3600 s 1 20 NEL Return Enable 0 1 0 0 Disable 1 Enable...

Page 29: ...tive Type 0 1 1 0 Output N O 1 Output N C 18 Combined 1 Or Output Contents 0 92 0 Not Used 19 Combined 2 or Output 1 Active Type 0 1 0 0 Output N O 1 Output N C 20 Combined 2 or Output 1 Contents 0 92...

Page 30: ...utput 2 Active Type 0 1 0 0 Output N O 1 Output N C 46 Combined 6 or Output 2 Contents 0 92 0 Not Used 47 Combined 6 or Output Active Type 0 1 0 0 Output N O 1 Output N C 48 Combined 6 or Output Conte...

Page 31: ...ar starting 6 S2 Genset Fault Input Prohibit S2 genset start when S2 genset has fault used in circular starting 7 Start Inhibit Input Prohibit genset start signal output In auto mode disconnect start...

Page 32: ...alarm occurs when it is active HVD100 voltage detection module as signal input is needed 32 Switch Output Voltage Abnormal Warn After this port is configured warning alarm occurs when it is active HV...

Page 33: ...Control Output before load is power off or switch transfer used to control running elevator to stop at the nearest level until transfer is finished 20 Fire Control Linkage Output when forced to open...

Page 34: ...Blackout S1 power status 65 S1 Over Volt 66 S1 Under Volt 67 S1 Over Freq 68 S1 Under Freq 69 S1 Loss Of Phase 70 S1 Phase Seq Wrong 71 Reserved 72 Reserved 73 S2 Blackout S2 power status 74 S2 Over V...

Page 35: ...e Contents of AND condition output SW3 Input port 3 is active Close when AND condition output SW3 is active inactive close when active disconnect when inactive Output result is as below When input por...

Page 36: ...2 power status Record date and time Press to check the detailed information of current records Action Event 010 200 Closing S2 Record type serial No total record number Record event S1 phase voltage S...

Page 37: ...and Power of current time point Press or to exit the detailed data interface Closing S2 19 09 28 10 07 18 10s Record event Record time point S1 power status S1 phase voltage S1 frequency S1 Available...

Page 38: ...c display of U1 A phase voltage 15 19 times harmonic display of U1 A phase voltage 21 times harmonic display of U1 A phase voltage 13 AUTO RESTORE TIME SETTING In menu page select 6 Auto Restore Time...

Page 39: ...troller is in the auto mode Under auto mode the controller will switch automatically to ensure power supply for loading according to S1 S2 status switch priority and Auto Trans Restore status The foll...

Page 40: ...HAT600P Series ATS Controller User Manual Page 40 of 58 14 2 2 AUTO TRANSFER NON RESTORE MUTUAL BACKUP ACTIVE Fig 7 Auto Transfer Non Restore Diagram Mutual Backup Active...

Page 41: ...FER NON RESTORE MUTUAL BACKUP INACTIVE Fig 8 Auto Transfer Non Restore Diagram Mutual Backup Inactive NOTE Master power S1 close needs to transfer to manual mode by close operation key otherwise in au...

Page 42: ...ly phase difference shall not be set too big Otherwise load impact will be too big at closing Fail To Sync Action Warning alarm or fault alarm can be set after sync failure it continues waiting for sy...

Page 43: ...lse output At the same time S2 open pulse outputs until S2 open status is detected or delay is over sync close open detection time disconnect S2 open pulse outputs In synchronizing process if close op...

Page 44: ...stopped If sync waiting is overtime sync failure warning alarm is initiated but it will continue waiting to sync until sync is completed or cancel sync close by pressing close key 14 3 4 AUTO SYNC CL...

Page 45: ...ply 16 The upper and lower thresholds of AC supply voltage meets requirements 17 ATS supply power of output port setting is phase voltage or line voltage For example taking ATS power supply as phase v...

Page 46: ...nnection set value after the auto reconnection delay NEL3 will be reconnected for the earliest and next is NEL2 NEL1 Fig 11 NEL Control Time Sequence 16 3 MANUAL TRIP If NEL manual trip input is activ...

Page 47: ...PS 17 2 RS485 COMMUNICATION PORT Communication Protocol Modbus RTU Communication Parameters Module address 1 range 1 254 Baud rate 9600 bps 2400 4800 9600 19200bps Data bit 8bit Parity bit None None O...

Page 48: ...Description Pin Items Description Notes 1 S1 close output Volt free relay N O output 250VAC 16A capacity 2 3 S2 close output Volt free relay N O output 250VAC16A capacity 4 5 Aux output 1 N C Default...

Page 49: ...free relay N O output Default S2 open control Capacity 8A 250VAC 30 31 Aux output 5 Voltage free relay N O output Default self defined combination output 1 Capacity 8A 250VAC 32 42 Aux output 6 Volta...

Page 50: ...ION 18 2 1 DC SUPPLY HAT600P series controller are all DC supply fitted with supply voltage range 8 35 VDC Fig 16 DC Supply 18 2 2 AC SUPPLY HAT600PB HAT600PBI HAT600PS controllers are AC supply fitte...

Page 51: ...d Adapter connection is as below Fig 18 RS485 Connection 19 TYPICAL APPLICATION WIRING DIAGRAM Fig 19 SGQ N T Application Diagram Table 23 Related Settings Part of Parameter Settings Switch Type Setti...

Page 52: ...User Manual Page 52 of 58 Fig 20 SGQ M Application Diagram Table 24 Related Settings Part of Parameter Settings Switch Type Setting PC two stage Aux Output 1 ATS Power L Aux Output 2 ATS Power N Aux...

Page 53: ...ge 53 of 58 Fig 21 AtyS d Application Diagram Table 25 Related Settings Part of Parameter Settings Switch Type Setting PC three stage Aux Output 1 ATS Power L Aux Output 2 ATS Power N Aux Output 3 S1...

Page 54: ...22 Feiteng Application Diagram Table 26 Related Settings Part of Parameter Settings Switch Type Setting CB Class CC Class Aux Output 1 ATS Power L Aux Output 2 ATS Power N Aux Output 3 S1 Open Output...

Page 55: ...ler User Manual Page 55 of 58 Fig 23 Contactor Application Diagram Table 27 Related Settings Part of Parameter Settings Switch Type Setting CB Class CC Class Aux Output 6 Genset Start Output Close Con...

Page 56: ...ut 3 S1 Open Output Aux Output 4 S2 Open Output Aux Output 6 Genset Start Output NOTE 1 Above are HAT600P series function application diagrams among which HAT600P HAT600PB are not current sampling inp...

Page 57: ...g 26 Clip Installation Illustration NOTES CAUTION Risk of electric shock Please cut off the power of the controller before maintenance WARNING Risk of electric shock Do not remove the rear shell of th...

Page 58: ...r network wires are correctly connected Programmable output error Check programmable output connections pay attention to Normally opened and closed Check the output parameters settings and output type...

Reviews: