HAT600P Series ATS Controller User Manual Page 17 of 58
Table 12 Switch Status
No.
Status Name
Description
1
Ready to Transfer
Enter switch transfer process;
2
S1 Closing
S1 closing delay is in progress;
3
S1 Opening
S1 opening delay is in progress;
4
S2 Closing
S2 closing delay is in progress;
5
S2 Opening
S2 opening delay is in progress;
6
Transfer Rest
Interval time between switch transfers;
7
Closing S1 Again
It is the second closing time when the first S1 opening is
not successful;
8
Opening S1 Again
It is the second opening time when the first S1 closing is
not successful;
9
Closing S2 Again
It is the second closing time when the first S2 opening is
not successful;
10
Closing S2 Again
It is the second opening time when the first S2 closing is
not successful;
11
Waiting Synch.
Delay time for waiting S1/S2 to meet synch. conditions
(voltage difference, frequency difference, phase difference);
12
S1 Sync. Close
S1 synch. close outputs when sync. conditions are
satisfied;
13
S2 Sync. Close
S2 synch. close outputs when sync. conditions are
satisfied;
14
Waiting S1 PF
S1 is waiting for input setting (S1 gets ready/PF) is active
before S1 closes;
15
Waiting S2 PF
S2 is waiting for input setting (S2 gets ready/PF) is active
before S2 closes;
16
Elevator Delay
Delay time before switch transfer, elevator control outputs;
17
S1 On Load
S1 was already closed and S1 is taking load;
18
S2 On Load
S2 was already closed and S2 is taking load;
19
Offload
Switch was already opened and load is disconnected.
When controller detects warning alarm, warning alarm is active, alarm indicator will flash slowly (1 time
1 second); after warning is recovered, alarm indicator will extinguish. Warning alarm is not latched.
Table 13 Warning Alarms
No.
Status Name
Description
1
S1 Over Current Warn
Action is set to warning; current is over pre-set limit when
S1 is taking load;
2
S2 Over Current Warn
Action is set to warning; current is over pre-set limit when
S2 is taking load;
3
Forced Open Warn
It alarms when the forced open (Non-firefighting cutoff
input) action is warning, and the forced open input is active;
4
Battery Under Volt
Battery voltage is lower than the set limit value;
5
Battery Over Volt
Battery voltage is higher than the set limit value;
6
Fail to Sync. Warn
Sync. failure action is set to warning, and it alarms when
sync. delay is over time;
7
Switch Output Voltage
Abnormal
Input port is configured to "Output Voltage Abnormal Warn",
and when the input is active, warning occurs.
8
Busbar Voltage Abnormal
Input port is configured to “Busbar Voltage Abnormal
Warn”, and when the input is active, warning occurs.