HAT600P Series ATS Controller User Manual Page 28 of 58
No.
Item
Range
Default
Description
7
Over Current Enable (0~1)
1
0: Disable
1: Enable
8
Over Current
(0~200)%
120
Limits for over current;
9
Over Current
Protection
(0~1)
0
0: Warn
1: Trip
10
Over Current Type
(0~1)
0
0: Definite
1: Inverse Definite
11
Definite Delay Set
(Value)
(0~3600)s
10
Over current delay value for definite
time;
12
Inverse Delay Set
(Multiplier)
(1~36)
36
Over current delay multiplier for inverse
definite;
13
Elevator Enable
(0~1)
0
0: Disable
1: Enable
14
Elevator Delay
(0~300)s
300
Delay time for load power off or before
switch transfer; used to control the
running elevator stop at the nearest
level until switch transfer is finished;
15
NEL Enable
(0~1)
0
0: Disable
1: Enable
16
NEL Over Power Val
1
(0~200)%
90
When load power is over the set value,
unload control outputs after delay;
17
NEL Over Power
Delay 1
(0~3600)s
5
18
NEL Over Power Val
2
(0~200)%
100
When load power is over the set value,
unload control outputs after delay;
19
NEL Over Power
Delay 2
(0~3600)s
1
20
NEL Return Enable
(0~1)
0
0: Disable
1: Enable
21
NEL Return Value
(0~200)%
50
When load power is lower than the set
value, unload control is disconnected
after delay;
22
NEL Return Delay
(0~3600)s
5
23
NEL Nums
(1~3)
3
NEL numbers;
24
Mains Load NEL
Enable
(0~1)
0
0: Disable
1: Enable
Digital Input Settings
1
Digital Input 1
(0~39)
1
Forced Open
2
Active Type
(0~1)
0
0: Close to activate;
1: Open to activate
3
Digital Input 2
(0~39)
8
Switch trip input
4
Active Type
(0~1)
0
0: Close to activate;
1: Open to activate
5
Digital Input 3
(0~39)
0
Not Used
6
Active Type
(0~1)
0
0: Close to activate;
1: Open to activate
7
Digital Input 4
(0~39)
0
Not Used
8
Active Type
(0~1)
0
0: Close to activate;
1: Open to activate
Digital Output Settings
1
Digital Output 1
Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
2
Digital Output 1
(0~92)
49
ATS power L1
3
Digital Output 2
Active Type
(0~1)
0
0: Output (N/O);
1: Output (N/C)
4
Digital Output 2
(0~92)
52
ATS power N