HAT600P Series ATS Controller User Manual Page 18 of 58
When controller detects fault alarm, fault alarm is active, alarm indicator will flash fast (5 time per
second); Fault alarm is latched and it can be removed until reset it manually.
Table 14 Fault Alarms
No.
Status Name
Description
1
S1 Failed to Close
S1 fails to close when it closes in auto mode;
2
S1 Failed to Open
S1 fails to open when it opens in auto mode;
3
S2 Failed to Close
S2 fails to close when it closes in auto mode;
4
S2 Failed to Open
S2 fails to open when it opens in auto mode;
5
S1 Load Over Current Trip
Action is set to trip; current is over preset limit when S1 is
taking load;
6
S2 Load Over Current Trip
Action is set to trip; current is over preset limit when S2 is
taking load;
7
Forced Open Fault
It alarms when the forced open (Non-firefighting cutoff
input) action is fault, and the forced open input is active;
8
S1 Genset Fault
S1 cannot start normally when system is S1-Gen S2-Gen;
9
S2 Genset Fault
S2 cannot start normally when system is S1-Gen S2-Gen;
10
Breaker Trip Alarm
Breaker trip alarm input is active.
11
Sync Fail Fault
Sync. failure action is set to fault, when it is over delay time,
fault alarms;
12
S1/S2 Close At the same
time
It alarms when S1 close signal input and S2 close signal
input are active at the same time for over 300ms;
13
S1 Load End Dead
Fault alarms when S1 closes but load end is dead for over
1min (load voltage monitoring enabled);
14
S2 Load End Dead
Fault alarms when S2 closes but load end is dead for over
1min (load voltage monitoring enabled);
15
Switch Output Voltage
Abnormal
Input is configured to "Output Voltage Abnormal Fault", and
when input is active, fault alarms.
When indication information is active, it disappears after it displays for 2s.
Table 15 Indication Information
No.
Status Name
Description
1
Please reset the alarm
Reminder information for switching to auto mode manually
before alarm is removed when fault alarm occurs;
2
S1 was already closed
In manual mode, the indication information for pressing S2
close key when S1 has been closed;
3
S2 was already closed
In manual mode, the indication information for pressing S1
close key when and S2 has been closed;
4
Panel Button Latched
When “panel button latched” input is active, it is the
reminder information for pressing panel button (Auto key,
Manual key, S1 Close key, S2 Close key, Open key, Alarm
Reset key).