HAT600P Series ATS Controller User Manual Page 49 of 58
Pin
Items
Description
Notes
13
C1
14
N1
15
A2
S2 AC 3-phase 4 wire voltage input
For single phase, only connect
A2, N2
16
B2
17
C2
18
N2
19
B-
Connects genset start battery
negative;
Module GND connected terminal
20
B+
Connects genset start battery
positive when genset is started;
DC
positive
input
(8-35)V,
controller power
21
S1 close input
Detection of S1 switch closing
state, voltage free contact input
GND connected is active;
22
S2 close input
Detection of S2 switch closing
state, voltage free contact input
GND connected is active;
23
Aux. input 1
User defined
Default: Forced Open
GND connected is active;
24
Aux. input 2
Default: Breaker Trip Input
GND connected is active;
25
Aux. input 3
Default: Not Used
GND connected is active;
26
Aux. input 4
Default: Not Used
GND connected is active;
27
Aux. output 3
Voltage free relay N/O output
Default: S1 open control
Capacity 8A 250VAC
28
29
Aux. output 4
Voltage free relay N/O output
Default: S2 open control
Capacity 8A 250VAC
30
31
Aux. output 5
Voltage free relay N/O output
Default: self defined combination
output 1; Capacity 8A 250VAC
32
42
Aux. output 6
Voltage free relay N/C output
Default: genset start output
Capacity 8A 250VAC
43
36
IA Input
Input of CT Secondary phase A
current
Rated current 5A
Only
suitable
for
HAT600PI/HAT600PBI/HAT600P
S
37
IA Output
38
IB Input
Input of CT Secondary phase B
current
39
IB Output
40
IC Input
Input of CT Secondary phase C
current
41
IC Output
44
120Ω Resistor
Match
resistor
for
RS485
resistance
Users need to connect this
terminal with terminal 33 based
on the on-site situation to
connect this 120 Ω resistor into
the controller.
33
RS485 communication port
34
RS485 B-
35
PE
GND Connected terminal for
communication port
45
A3
Voltage input on load end
(50VAC-360VAC)
When load end wiring is being
done, parameter "Load Volt.
Monitor" is enabled; controller
default is disabled;
47
N3
USB
USB
D form USB communication port
Able to connect PC to configure
parameters
and
software
upgrade;
ETHERNET Ethernet port
Used for communication
Only
suitable
for
HAT600PBI/HAT600PS;