HAT600P Series ATS Controller User Manual Page 24 of 58
No.
Item
Range
Default
Description
19
Over Frequency Set
(0-1)
1
0: Disable
1: Enable
20
Set Value
(0-200)%
110
Upper limit value of frequency; it is
abnormal if the value has exceeded the
set value.
21
Return Value
(0- 200)%
104
Upper limit return value of frequency; it
is normal only when the value has fallen
below the set value.
22
Under Frequency Set (0-1)
1
0: Disable
1: Enable
23
Set Value
(0- 200)%
90
Lower limit value of frequency; it is
abnormal if the value has fallen below
the set value.
24
Return Value
(0- 200)%
96
Lower limit return value of frequency; it
is normal only when the value has
exceeded the set value.
25
Phase Sequence
Wrong
(0-1)
1
0: Disable
1: Enable
26
Load Volt Enable
(0-1)
0
0: Disable
1: Enable
Switch Settings
1
Definite C/O Time
(0~1)
0
0: Disable
1: Enable
Disable: Detect output time according to
close status when close/open pulse
outputs; longest time is the set time;
Enable: close/open pulse output time is
the set close/open time;
2
Close Time
(0.1~20.0)s
5.0
Outputted pulse time of close relay;
3
Open Time
(0.1~20.0)s
5.0
Outputted pulse time of open relay;
4
Transfer Time
(0~9999)s
1
Delay time from S1 open to S2 close; or
from S2 open to S1 close;
5
Again Close Time
(0-20.0)s
1.0
If the first switch open is not successful,
then the second close starts and again
close delay starts; when the delay is
over, then the second open starts; if the
open cannot be conducted, then open
failure alarm signal shall be sent out;
6
Again Open Time
(0-20.0)s
1.0
If the first switch close is not
successful, then the second open starts
and again open delay starts; when the
delay is over, then the second close
starts; if the close cannot be conducted,
then close failure alarm signal shall be
sent out;
7
Switch Type
(0~2)
0
0: CB/CC (S1 Open and S2 Open
control is needed.)
1: PC Three-stage (For PC switch with
neutral, S1 open control is needed.)
2: PC Two-stage (For PC switch
without neutral)
8
Forced Open Action
(0-1)
0
0: Warn Alarm
1: Fault Alarm
9
Continually Close
(0~1)
0
0: Disable
1: Enable