HI302 – User’s Manual
A.4
Index
Parameter
Data Type
Valid Range / Options
Default Value
Units
Store/Mode
Description
HART
Read
Hart
Write
22
UNIQUE_ID
OctString(5)
{0, 0, 0, 0, 0}
NA
D / RO
Device's Unique ID (MAN_ID, DEV_TYPE, DEV_ID).
(0, 11, 21)
23
COMM_ERR
BitString(8)
0x01:
Undefined
0x02:
Buffer Overflow
0x04:
Reserved
0x08:
Longitudinal Parity
Errorr
0x10:
Framing Error
0x20 :
Overrun Error
0x40
: Vertical Parity Error
0x80:
Comm Error
0x00
None
D / RO
First byte of the last transaction Response Code if
communication error has occurred (Bit7 = 1).
All
All
24
RESP_CODE
Unsigned8
0x00
None
D / RO
Command result (no communication error, Bit7 = 0).
The command result is highly command and device
dependent. See the device's manual.
All
All
25
DEVICE_STATUS
BitString(8)
0x01:
Primary Variable Out
of Limits
0x02:
Non-Primary Variable
Out of Limits
0x04:
Loop Current
Saturated
0x08:
Loop Current Fixed
0x10:
More Status Available
0x20:
Cold Start
0x40:
Configuration
Changed
0x80:
Device Malfunction
0
NA
D / RO
Second byte of the last transaction Response Code.
All
All
26
MAN_ID
Enumerated
HC TABLE 8
0
None
D / RO
Manufacturer ID Code.
(0, 11, 21)
27
DEV_TYPE
Unsigned8
0
None
D / RO
Manufacturer Device Type Code.
(0, 11, 21)
28
MNP_REQ
Unsigned8
0
None
D / RO
Minimum Number of Preambles from Master to
Slave.
(0, 11, 21)
29
UNI_REV
Unsigned8
0
None
D / RO
Revision Level of the Universal Command.
(0, 11, 21)
30
SPEC_REV
Unsigned8
0
None
D / RO
Revision Level of the Device Specific.
(0, 11, 21)
31
SW_REV
Unsigned8
0
None
D / RO
Software Revision Level.
(0, 11, 21)
32
HRDW_REV
Unsigned8
0
None
D / RO
Hardware Revision Level.
(0, 11, 21)
33
FLAGS
BitString(8)
HC TABLE 11
0
NA
D / RO
Flags (manufacturer specific).
(0, 11, 21)
34
DEV_ID
OctString(3)
{0, 0, 0}
NA
D / RO
Device ID Number.
(0, 11, 21)
35
MNP_RSP
Unsigned8
0
None
D
Minimum Number of Preambles from Slave to
Master.
(0, 11, 21)
59
36
MAX_VAR
Unsigned8
0
None
D / RO
Maximum Number of Device Variables.
(0, 11, 21)
37
CFG_COUNT
Unsigned16
0
None
D / RO
Configuration Change Counter.
(0, 11, 21)
38
EXT_STATUS
Bistring(8)
HC TABLE 17
0
None
D / RO
Extended Field Device Status.
(0, 11, 21)
39
PV_MA
DS-65
0
mA
D
PV Current Output Value (milliamperes).
PV_MA.VALUE
: loop mA actual value,
PV_MA.STATUS
: HART Response Code.
2
40
LOOP_TEST
Float
0
mA
D
Enter/Exit PV fixed current mode. Read the result in
RESP_CODE.
40
41
LOOP_CMODE
Enumerated
HC TABLE 16
0
None
D
Loop Current Mode.
7
6
42
PV_PERC
DS-65
0
%
D / RO
PV Percent of Range.
PV_PERC.VALUE
: the percentual Pv value,
PV_PERC.Status
: HART Response Code.
2
43
PV_CLASS
Enumerated
HC TABLE 21
0
None
D / RO
PV Classification.
8
44
PV_UC
Enumerated
HC TABLE 2
0
None
D
PV Units Code.
15
44
45
PV_VAL
DS-65
0
PV_UC
D / RO
PV_VAL.Value
: actual PV value in engineering
units,
PV_VAL.Status
: HART Response Code.
3
Summary of Contents for HI302
Page 1: ...AGO 02 FOUNDATION H I 3 2 F M E...
Page 4: ...HI302 User s Manual IV...
Page 10: ...General Vision 1 4...
Page 20: ...Installation 2 10...
Page 46: ...Operation 5 12...
Page 57: ...HI302 User s Manual 7 5...
Page 59: ...HI302 User s Manual 7 7...
Page 60: ...An Example of HI302 Usage 7 8...
Page 64: ...Troubleshooting 8 4...