No.
Name
Description
Value
Explanation
Default
Value
234.11
GnErrStpTm
Idle time after generator
error in hours (expert
mode)
0 h to 24 h
‒
✖
✓ 1 h
234.12
GnWarmTm
Warm-up time in seconds 5 s to 900 s
‒
✖
✓ 60 s
234.13
GnRvPwr
Maximum reverse power
for voltage monitoring of
generator in W (expert
mode)
0 W to 5000 W
One Sunny Island
or single-cluster
system
✖
✓ 100 W
0 W to 20000 W
Multicluster sys-
tem
100 W
234.14
GnRvTm
Time for reverse power
or reverse current for
voltage monitoring of
generator in s (expert
mode)
0 s to 900 s
‒
✖
✓ 30 s
234.15
GnCtlMod
Type of generator cur-
rent limitation (expert
mode)
The generator control
limits the consumption of
generator current.
Cur
Fixed threshold
for current limita-
tion
✖
✓ Cur
CurFrq
Frequency-depen-
dent current limi-
tation
234.20
GnAlSns
Anti-islanding Sensitivity
of the generator fault
recognition (expert
mode)
Low
Low
✖
✓ Standard
Medium
Medium
Standard
Standard
High
High
234.41
GnCurCtlMo
d
Enable I‑Loop in genera-
tor operation (expert
mode, only with
SI6.0H-11 and
SI8.0H-11)
I‑Loop enables genera-
tors with inadequate volt-
age regulation to be
used in the system.
Droop
Standard genera-
tor operation with-
out I‑Loop
✖
✓ Droop
CurCtl
Current-controlled
generator opera-
tion with I‑Loop
234.42
GnAIFac
Anti-islanding factor in
current-controlled gener-
ator operation with I-
Loop (expert mode)
0.00 to 1.00
–
✖
✓ 0.10
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
138