No.
Name
Description
Value
Explanation
Default
Value
232.43
P-HzStop
Difference between re-
set frequency and grid
frequency, linear instan-
taneous power gradient
configuration (protected
by SMA Grid Guard)
0.0 Hz to 5.0 Hz
This values defines
how many Hz above
210.02 InvFrqNom
the active power limi-
tation stops.
✓
✖ 0.2 Hz
232.44
P-WGra
Active power gradient,
linear instantaneous
power gradient configu-
ration (expert mode,
protected by
SMA Grid Guard)
10
%
⁄
Hz
to 130
%
⁄
Hz
–
✓
✓ 40%⁄Hz
232.46
WGraRecon
Power gradient follow-
ing grid error in % (ex-
pert mode, protected
by SMA Grid Guard)
1% to 100%
‒
✓
✓ 10 %
232.48
Q-VArMod
Operating mode of
static voltage stability,
configuration of static
voltage stability (expert
mode, protected by
SMA Grid Guard)
Off
Disable
✓
✓
–
PFCnst
Constant displace-
ment power factor
cos φ
PFCtlW
Automatic adaptation
of the displacement
power factor accord-
ing to the current ac-
tive power
232.49
PF-PF
CosPhi setpoint, cosPhi
configuration, direct
specification (expert
mode, protected by
SMA Grid Guard)
0.8 to 1
Code of Practice
VDE-AR-N 4105
✓
✓ 0.9
Norm AS-4777
1
232.50
PF-PFExt
CosPhi excitation type,
cosPhi configuration, di-
rect specification (ex-
pert mode, protected
by SMA Grid Guard)
OvExt
Lagging
✓
✓ UnExt
UnExt
Leading
232.51
PF-PFStr
CosPhi of the start
point, configuration of
cos Phi(P) characteristic
curve, direct specifica-
tion (expert mode, pro-
tected by
SMA Grid Guard)
0.8 to 1
–
✓
✓ 1
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
133
SI30M-44M-60H-80H-BE-en-33
Summary of Contents for SUNNY ISLAND 3.0M