133# Gen State
No.
Name
Description
Value
(Plain text
no.)
Explanation
133.01
GnDmdSrc
Reason for requesting genera-
tor:
None (1)
No request
✖
✓
Bat (2)
State-of-charge-dependent re-
quest
Lod (3)
Load-dependent request
Tim (4)
Time-controlled request
Run1h (5)
Requested for 1 hour
Start (6)
Manually started
ExtSrcReq (7)
External generator request
133.02
GnStt
Generator state
Off (1)
Deactivated generator opera-
tion
✖
✓
Init (2)
Detecting generator
Ready (3)
Waiting for request (ready)
Warm (4)
Warming up
Connect (5)
Connecting
Run (6)
Operation
Retry (7)
Restarting
Disconnect (8)
Split
Cool (9)
Cooling down
Lock (10)
Locked after operation
Fail (11)
Error
FailLock (12)
Locked after error
Reinit (13)
Re-detection of the generator
133.03
GnRmgTm
Remaining minimum run time of
the generator in hh:mm:ss
–
–
✖
✓
133.04
GnRnStt
Status of the digital input for
generator feedback (expert
mode)
Off (1)
Off
✖
✓
On (2)
On
134# Device
No.
Name
Description
134.01
ExtPwrAt
Total active power of the external grid connection at line conductor L1 in kW
✖
✓
134.02
ExtVtg
Voltage of the external grid connection at line conductor L1 in V
✖
✓
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
115
SI30M-44M-60H-80H-BE-en-33