No.
Name
Level Cause
Corrective measures
W 738 GnSynLoss
1
Synchronization with the gener-
ator not successful.
• Ensure that the generator can be
started. The fuel level may be too
low.
• Ensure that a constant and stable
voltage is present at connection
AC2
.
• Ensure that the thresholds for the
generator voltage are correctly
configured.
F 739 SPICom
3
No message from the device
at L1: Internal device communi-
cation of the master is disturbed.
• Contact the Service (see Section 16
W 740 SPIComSlv1
1
No message from the device
at L2: Internal device communi-
cation of slave 1 is disturbed.
W 741 SPIComSlv2
1
No message from the device
at L3: Internal device communi-
cation of slave 2 is disturbed.
F 743 CANCom
3
Internal CAN communication is
missing in the device at L1
(Master).
• Contact the Service (see Section 16
• Ensure that the terminators in the
communication bus are attached.
• Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
W 744 CANComSlv1
1
Internal CAN communication is
missing in the device at L2
(slave 1).
W 745 CANComSlv2
1
Internal CAN communication is
missing in the device at L3
(slave 2).
W 747 InvTmpSnsSlv1
1
Short circuit or cable break on
the temperature sensor of the
transformer L2 (slave 1).
• Contact the Service (see Section 16
W 748 InvTmpSnsSlv2
1
Short circuit or cable break on
the temperature sensor of the
transformer L3 (slave 2).
W 750 InvTmpSnsSlv1
1
Short circuit or cable break on
the temperature sensor of the in-
verter bridge L2 (slave 1).
• Contact the Service (see Section 16
W 751 InvTmpSnsSlv2
1
Short circuit or cable break on
the temperature sensor of the in-
verter bridge L3 (slave 2).
10 Troubleshooting
SMA Solar Technology AG
Operating Manual
71
SI30M-44M-60H-80H-BE-en-33