DOL 434 LPV
52
Technical Manual
Integration time (long)
Reaction to too low humidity.
Longer time = slow ventilation build-up.
Shorter time = faster ventilation build-up.
Differential factor
Differential time for humidity ventilation.
Short time = modest reaction.
Long time = strong reaction.
for a general description of PID regulation.
6.5.5.1.3 Humidity control at adaptive heat mode
Control mode
At humidity control according to the principle Humidity heat.
Select Adaptive - self learning for the humidity heat to automatically adapt to the
conditions in the house in question.
Adaption time is set in the menu
Climate | Humidity | Settings | Adaptive
reaction for heat
.
The function is only available when a heat source and a humidity sensor are in-
stalled.
See section
for a general description of adaptive control.
6.5.5.1.4 Humidity control at PID heat mode
P band
The proportional band according to which heating is controlled.
Integration time (short)
Reaction to too high humidity.
Long time = slow heat supply.
Short time = fast heat supply.
Integration time (long)
Reaction to too low humidity.
Long time = slow heat supply.
Short time = fast heat supply.
Differential time
Differential time for humidity heat.
Short time = modest reaction.
Long time = strong reaction.
for a general description of PID regulation.
6.5.5.2 Humidification
Cycle time
ON + OFF-time of the humidification relay.
Minimum ON time
With humidification requirement: The relay is ON for minimum this time.
P band
The proportional band according to which humidification is controlled.
Integration time
Reaction time for humidification.
Short time: Immediate reaction.