DOL 434 LPV
Technical Manual
27
5 Testing
After installation of the system a thorough test must be carried out, to ensure that the system works as intended.
5.1 Testing basis components
5.1.1 Testing temperature and air humidity sensors
Read the current inside temperature and humidity
1. Check that the temperature displayed corresponds to what you can measure in the house/outside.
2. Check that the temperature increases in the display when you warm the sensor in your hand.
3. Check that the humidity displayed corresponds to what you can measure in the house.
4. Check that the humidity rises when you breathe on the sensor, for example.
5.1.2 Testing Alarm
Select
Alarm settings
.
Activate
Alarm test
to start testing.
Check that the alarm lamp is flashing.
Check that the alarm system alarms as intended.
Press
Acknowledge
to finish testing.
The test should then be made every week.
5.1.3 Testing emergency opening
See the Technical Manual for the emergency opening.
5.2 Testing optional components: Manual control
During testing, and in a service situation, the individual components connected to the climate or production con-
troller and be switched from automatic to manual control. Thus, you can easily test the optional components
such as winch motors, etc.
In the menu
Manual/auto
the house controller displays the components selected in the menu
Installation
.
Automatic control:
Normally the controller must be set to automatic control.
Manual mode:
During start up, or in a service situation, it may be convenient to control the individual functions
manually.