Maintenance
Service Manual
7 Maintenance
Cleaning
Before any maintenance, unplug the cabinet from the power supply.
Cabinet
Periodically wipe the inside and outside of the cabinet with a damp cloth, taking care to keep
moisture away from electrical parts.
Condenser
Filter and Coil
To ensure trouble-free performance, SKOPE strongly recommends that the condenser filter
and coil are cleaned:
every month with a soft brush to remove dust and fluff.
every six months, by qualified service personnel.
The condenser coil and air filter
must
be kept clean for efficient and reliable operation.
WARNING
Unplug the fridge from the power supply before cleaning the
condenser coil.
Procedure 30: To clean the condenser filter
1. Disconnect the cabinet from the power supply (see page 18).
2. To remove the filter, use the finger
loops to pull the filter up and detach
from the front panel.
3. Clean the filter with a vacuum cleaner, wash with cold water and shake excess water off before
refitting. Do not apply hot water, blow dry or place in dishwasher. If necessary, discard and refit
new air filter.
4. To refit the filter, insert it up into the locating bracket on the top face of the front panel vent with
the finger loops facing out. Clip into the slots on the bottom face of the front panel vent.
Procedure 31: To clean the condenser coil
1. Disconnect the cabinet from the power supply (see page 18).
2. Remove the kick panel (see page 19).
3. Gently brush the face of the condenser coil to remove any debris, and straighten any bent fins
using a fin comb.
4. Once clean, refit the kick panel (see page 19).
Air filter
Finger loops