Replacement Procedures
Service Manual
4. Unscrew and remove the cartridge’s left hand side panel to access the condenser probe.
5. Detach the probe from the condenser coil.
Trace the probe cable to the cartridge electrics
box and unplug it.
6. Following the same path as the original probe, run the new probe to the condenser coil and
secure with cable ties. Use cork tape to insulate the probe. Ensure the probe cable is securely
plugged into the rear of the cartridge electrics box.
7. Reassemble the cartridge and test and tag as per standard procedure.
8. Reconnect to the power supply and check for correct operation.
Procedure 29: To replace the condenser probe (continued)
Condenser probe