Replacement Procedures
Service Manual
SKOPE OD1100N
Condenser
Probe
The condenser probe is located on the side of the condenser coil.
8. Reassemble the cartridge and test and tag as per standard procedure.
9. Reconnect to the power supply and check for correct operation.
Procedure 28: To replace the evaporator probe
Before you start
Make sure you take note of the original evaporator probe cable’s path.
1. Disconnect the cabinet from the power supply (see page 18).
2. Remove the refrigeration cartridge (see page 28).
3. Remove the cartridge’s right side panel.
4. Remove the electrics box cover.
5. Unplug the evaporator probe from the electrics box (black plug).
6. Remove the evaporator probe from the cartridge, cutting cable ties where necessary.
7. Following the same path as the
original probe, run the new probe to
the original location and secure with
cable ties.
8. Push the probe between the fins
above the bottom tube,
approximately 100 mm from the end
(25 fins). Close the fins behind the
probe.
9. Reassemble the cartridge and test and tag as per standard procedure.
10. Reconnect to the power supply and check for correct operation.
Procedure 27: To replace the control probe (continued)
Procedure 29: To replace the condenser probe
Before you start
Make sure you take note of the original condenser probe cable’s path.
1. Disconnect the cabinet from the power supply (see page 18).
2. Remove the refrigeration cartridge (see page 28).
3. Carefully lift the evaporator tub.