4.3.1 Outdoor
Unit
Capability of Air Swith Minimum Sectional Area of
Earth Wire
Minimum Sectional Area
of Power Supply Wire
(A)
(mm
2
)
(mm
2
)
ASGE-09A WK
220-240, 1
,
50
16
2,5
2.5
ASGE-12A WK
220-240, 1
,
50
16
2,5
2.5
ASGE-18A WK
220-240, 1
,
50
20
4.0
4.0
ASGE-24A WK
220-240, 1
,
50
25
4.0
4.0
ASGE-36A WK
380-415, 3
,
50
16
2,5
2.5
ASGE-42A WK
380-415, 3
,
50
20
4.0
4.0
ASGE-48A WK
380-415, 3
,
50
25
4.0
4.0
ASGE-60A WK
380-415, 3
,
50
25
4.0
4.0
• Duct Type
Capability of Air Swith Minimum Sectional Area of
Earth Wire
Minimum Sectional Area
of Power Supply Wire
(A)
(mm
2
)
(mm
2
)
ASDU-09A
220-240, 1
,
50
6
1.0
1.0
ASDU-12A
220-240, 1
,
50
6
1.0
1.0
ASDU-18A
220-240, 1
,
50
6
1.0
1.0
ASDU-24A
220-240, 1
,
50
6
1.0
1.0
ASDU-36A
220-240, 1
,
50
10
1.5
1.5
ASDU-42A
220-240, 1
,
50
10
1.5
1.5
ASDU-48A
220-240, 1
,
50
10
1.5
1.5
ASDU-60A
220-240, 1
,
50
10
1.5
1.5
•
Ceiling Type
Capability of Air Swith Minimum Sectional Area of
Earth Wire
Minimum Sectional Area
of Power Supply Wire
(A)
(mm
2
)
(mm
2
)
ASFU-09A
220-240, 1
,
50
6
1.0
1.0
ASFU-12A
220-240, 1
,
50
6
1.0
1.0
ASFU-18A
220-240, 1
,
50
6
1.0
1.0
ASFU-24A
220-240, 1
,
50
6
1.0
1.0
ASFU-36A
220-240, 1
,
50
6
1.0
1.0
ASFU-42A
220-240, 1
,
50
6
1.0
1.0
ASFU-48A
220-240, 1
,
50
6
1.0
1.0
•
Cassette Type
Capability of Air Swith Minimum Sectional Area of
Earth Wire
Minimum Sectional Area
of Power Supply Wire
(A)
(mm
2
)
(mm
2
)
ASCU-12A
220-240, 1
,
50
6
1.0
1.0
ASCU-18A
220-240, 1
,
50
6
1.0
1.0
ASCU-24A
220-240, 1
,
50
6
1.0
1.0
ASCU-36A
220-240, 1
,
50
6
1.0
1.0
ASCU-42A
220-240, 1
,
50
6
1.0
1.0
ASCU-48A
220-240, 1
,
50
6
1.0
1.0
Model
Power Supply
(
V
,
Ph, Hz)
4.3.2 Indoor Unit
4.3 Specification of Power Supply Wire and Air Switch
Model
Power Supply
(
V
,
Ph, Hz)
Model
Power Supply
(
V
,
Ph, Hz)
Model
Power Supply
(
V
,
Ph, Hz)
Summary of Contents for ASCU-12A
Page 1: ...SERVICE MANUAL INDOOR UNITS ASCU A ASDU A ASFU A UNI ON OFF SERIE OUTDOOR UNITS ASGE A ...
Page 2: ......
Page 3: ...1 PRODUCT ...
Page 24: ...U MATCH AIR CONDITIONERS PRODUCT 23 5 PIPING DIAGRAM ...
Page 25: ...24 CONTROL ...
Page 26: ...U MATCH AIR CONDITIONERS CONTROL 25 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation ...
Page 27: ...U MATCH AIR CONDITIONERS CONTROL 26 1 2 Heating Operation ...
Page 45: ...U MATCH AIR CONDITIONERS CONTROL 44 5 2 4 Dimensions ...
Page 48: ...GREE COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 47 INSTALLATION ...
Page 59: ......
Page 91: ...Model ASFU 60A ...
Page 93: ...GREE COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 91 MAINTENANCE ...
Page 160: ...PARTS GUIDE CASSETTE FLOOR CEILING DUCT UNITS OUTDOOR UNITS UNI ON OFF ...
Page 161: ......
Page 165: ...MAINTENANCE 162 2 Model ASGE 24A ASGE 24A WK Exploded Views ...
Page 167: ...MAINTENANCE 165 3 Model ASGE 36A Exploded Views ...
Page 169: ...ASGE 36A WK ...
Page 172: ...MAINTENANCE 168 4 Model ASGE 42A ASGE 42A WK Exploded Views ...
Page 174: ...MAINTENANCE 171 5 Model ASGE 48A ASGE 48A WK Exploded Views ...
Page 176: ...Model ASGE 60A WK ...
Page 187: ...U MATCH AIR CONDITIONERS MAINTENANCE 174 6 Model ASDU 60A Exploded Views ...
Page 191: ...MAINTENANCE 186 2 Model ASCU 24A ASCU 36A ASCU 42A ASCU 48A Exploded Views ...
Page 194: ...MAINTENANCE 189 5 2 3 Ceiling Type 1 Model ASFU 09A ASFU 12A ASFU 18A Exploded Views ...
Page 197: ...MAINTENANCE 192 2 Model ASFU 24A Exploded Views ...
Page 200: ...MAINTENANCE 195 3 Model ASFU 36A ASFU 42A ASFU 48A Exploded Views ...