U-MATCH AIR CONDITIONERS INSTALLATION
84
The air-conditioning unit shall have special power supply line which shall be equipped with
electricity leakage switch and air switch, so as to deal with overload conditions.
The air-conditioning unit must have grounding to avoid hazard owing to insulation failure.
All fitting lines must use crimp terminals or single wire. If multiple twisted wires are
connected to terminal board, arc may arise.
All line connections must conform to the schematic diagram of lines. Wrong connection may
cause abnormal operation or damage of the air-conditioning unit.
Do not let any cable contact the refrigerant pipe, the compressor and moving parts such as
fan.
Do not change the internal line connections inside the air-conditioning unit. The
manufacturer shall not be liable for any loss or abnormal operation arising from wrong line
connections.
4.1.3 Power Cable Connection
1) Air-conditioning unit with single-phase power supply
①
Remove the front-side panel of the outdoor unit.
②
Pass the cable though rubber ring.
③
Connect the power supply cable to the “L, N” terminals and the grounding screw.
④
Use cable fastener to bundle and fix the cable.
2) Air-conditioning unit with 3-phase power supply
①
Remove the front-side panel of the outdoor unit.
②
Attach rubber ring to the cable-cross hole of the outdoor unit.
③
Pass the cable though rubber ring.
④
Connect the power cable to the terminal and earthing screws marked “L1, L2, L3 & N”.
⑤
Use cable fastener to bundle and fix the cable.
Caution:
For air-conditioner with auxiliary heater, it is required to connect the power cable to the “L1,
L2 L3”terminals and the grounding screw.
4.1.4 Connection of Signal Line of Wire Controller
Caution:
Take great care when carrying out the following connections, so as to avoid malfunction of
the air-conditioning unit because of electromagnetic interference.
The signal line of the wire controller must be separated from the power line and the
connecting line between the indoor unit and the outdoor unit.
◆
In case the unit is installed in a place vulnerable by electromagnetic interference, it is
better to use shielded cable or double-twisted cable as the signal line of the wire controller.
Open the cover of the electric box of the indoor unit.
Pull the signal cable of the wire controller through the rubber ring.
Summary of Contents for ASCU-12A
Page 1: ...SERVICE MANUAL INDOOR UNITS ASCU A ASDU A ASFU A UNI ON OFF SERIE OUTDOOR UNITS ASGE A ...
Page 2: ......
Page 3: ...1 PRODUCT ...
Page 24: ...U MATCH AIR CONDITIONERS PRODUCT 23 5 PIPING DIAGRAM ...
Page 25: ...24 CONTROL ...
Page 26: ...U MATCH AIR CONDITIONERS CONTROL 25 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation ...
Page 27: ...U MATCH AIR CONDITIONERS CONTROL 26 1 2 Heating Operation ...
Page 45: ...U MATCH AIR CONDITIONERS CONTROL 44 5 2 4 Dimensions ...
Page 48: ...GREE COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 47 INSTALLATION ...
Page 59: ......
Page 91: ...Model ASFU 60A ...
Page 93: ...GREE COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 91 MAINTENANCE ...
Page 160: ...PARTS GUIDE CASSETTE FLOOR CEILING DUCT UNITS OUTDOOR UNITS UNI ON OFF ...
Page 161: ......
Page 165: ...MAINTENANCE 162 2 Model ASGE 24A ASGE 24A WK Exploded Views ...
Page 167: ...MAINTENANCE 165 3 Model ASGE 36A Exploded Views ...
Page 169: ...ASGE 36A WK ...
Page 172: ...MAINTENANCE 168 4 Model ASGE 42A ASGE 42A WK Exploded Views ...
Page 174: ...MAINTENANCE 171 5 Model ASGE 48A ASGE 48A WK Exploded Views ...
Page 176: ...Model ASGE 60A WK ...
Page 187: ...U MATCH AIR CONDITIONERS MAINTENANCE 174 6 Model ASDU 60A Exploded Views ...
Page 191: ...MAINTENANCE 186 2 Model ASCU 24A ASCU 36A ASCU 42A ASCU 48A Exploded Views ...
Page 194: ...MAINTENANCE 189 5 2 3 Ceiling Type 1 Model ASFU 09A ASFU 12A ASFU 18A Exploded Views ...
Page 197: ...MAINTENANCE 192 2 Model ASFU 24A Exploded Views ...
Page 200: ...MAINTENANCE 195 3 Model ASFU 36A ASFU 42A ASFU 48A Exploded Views ...