U-MATCH AIR CONDITIONERS INSTALLATION
53
1.1.6 Drain Piping Work
1
)
Installation of Drainage Pipeline
A drainage outlet is located at both the left and right sides of the indoor unit. After selecting one drainage
outlet, the other outlet shall be blocked by rubber plug. Bundle the blocked outlet with string to avoid
l1eakage, and also use thermal insulation materials to wrap the blocked outlet.
When shipped out from factory, both the Drainage outlets are blocked by rubber plugs.
When connecting the drainage pipe with the unit, do not apply excessive force to the pipeline at the side of
the unit. The fixing position of the pipeline shall be near the unit.
Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When carrying out
connection, place the end of the PVC pipeline into the drainage hole. Use flexible drainage tube and tighten
it with thread loop. Never use adhesive to connect the drainage hole and the flexible drainage tube. (As
shown in Figure 1-1-9)
When the laid drainage pipe is used for multiple units, the common pipe shall be about 100mm lower than
the drainage outlet of each set of unit. A pipe with thicker wall shall be used for such purpose.
Sponge (gray)
Drain hose
Clamp
Clamp(attachment)
Sponge(attachment)
Below 4mm
Figure 1-1-9
2
)
Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system.
During the test, check if the water correctly flows through the pipelines. Carefully observe the joints to
ensure that there is no leakage. If the unit is to be installed in a new house, carry out testing before decorating
the ceiling.
3
)
Matters of Attention
The joint of Drainage Pipeline must not have leakage.
The Drainage Pipeline shall be installed with an inclining angel of 5
~
10°, so as to facilitate the drainage of
condensate. The joints of the Drainage Pipeline must be covered by thermal insulation materials to avoid
generation of exterior condensate. (As shown in Figure 1-1-10)
Summary of Contents for ASCU-12A
Page 1: ...SERVICE MANUAL INDOOR UNITS ASCU A ASDU A ASFU A UNI ON OFF SERIE OUTDOOR UNITS ASGE A ...
Page 2: ......
Page 3: ...1 PRODUCT ...
Page 24: ...U MATCH AIR CONDITIONERS PRODUCT 23 5 PIPING DIAGRAM ...
Page 25: ...24 CONTROL ...
Page 26: ...U MATCH AIR CONDITIONERS CONTROL 25 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation ...
Page 27: ...U MATCH AIR CONDITIONERS CONTROL 26 1 2 Heating Operation ...
Page 45: ...U MATCH AIR CONDITIONERS CONTROL 44 5 2 4 Dimensions ...
Page 48: ...GREE COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 47 INSTALLATION ...
Page 59: ......
Page 91: ...Model ASFU 60A ...
Page 93: ...GREE COMMERCIAL AIR CONDITION U MATCH AIR CONDITIONERS 91 MAINTENANCE ...
Page 160: ...PARTS GUIDE CASSETTE FLOOR CEILING DUCT UNITS OUTDOOR UNITS UNI ON OFF ...
Page 161: ......
Page 165: ...MAINTENANCE 162 2 Model ASGE 24A ASGE 24A WK Exploded Views ...
Page 167: ...MAINTENANCE 165 3 Model ASGE 36A Exploded Views ...
Page 169: ...ASGE 36A WK ...
Page 172: ...MAINTENANCE 168 4 Model ASGE 42A ASGE 42A WK Exploded Views ...
Page 174: ...MAINTENANCE 171 5 Model ASGE 48A ASGE 48A WK Exploded Views ...
Page 176: ...Model ASGE 60A WK ...
Page 187: ...U MATCH AIR CONDITIONERS MAINTENANCE 174 6 Model ASDU 60A Exploded Views ...
Page 191: ...MAINTENANCE 186 2 Model ASCU 24A ASCU 36A ASCU 42A ASCU 48A Exploded Views ...
Page 194: ...MAINTENANCE 189 5 2 3 Ceiling Type 1 Model ASFU 09A ASFU 12A ASFU 18A Exploded Views ...
Page 197: ...MAINTENANCE 192 2 Model ASFU 24A Exploded Views ...
Page 200: ...MAINTENANCE 195 3 Model ASFU 36A ASFU 42A ASFU 48A Exploded Views ...