86
007-4644-001
A: Specifications and Requirements
Power Requirements
Table A-2 lists the power requirements for the rack.
Power Distribution Units
The rack has two PDUs (power distribution units). Each PDU has its own power cord.
Due to limited space inside the rack, it may be easier to connect and route power cords
before installing the support rails and enclosures.
To ensure redundancy, connect the PDUs in the rack to independent power circuits.
Connect one power cord from each enclosure to each PDU in the rack (see Figure A-5).
Table A-2
AC Power Requirements (Domestic and International)
Unit of Measure
Requirement
AC distribution, 250 VAC, 16 A
Approved IEC 320-C19 connector
Domestic, 250 VAC, 30 A
NEMA L6-30P locking plug, 6-30R receptacle (2)
International, 230 VAC, 32 A
IEC 309 locking plug; IEC 309 receptacle (2)
Voltage range
180 to 257 VAC
Frequency
49 to 50.5 Hz or 59 to 60.6 Hz
Current specified at volt/freq
220/50/60
Circuit breaker
25 A