Instruction Manual ScrubberGuard
Operation
46
14830E/1
7
Operation
7.1
Control elements of the ScrubberGuard on the cabinet
The ScrubberGuard is controlled via four control elements located on the cabinet. These are
three buttons plus a control input for external actuation. Only one control element may be
active at any one time. Activation is confirmed by the respective button lighting up. If multi-
ple functions are activated, this leads to a fault that is signaled by the flashing buttons. To
rectify this problem, all functions must be deactivated.
In order to ensure correct operation, the AquaScat SG (A) must be connected and the com-
munication between the AquaScat SG (A) and cabinet must be established.
Main switch
: The main switch is
used to switch the system on and
off.
Figure 15: Control elements for the ScrubberGuard
Remote Signal
(signal lamp): Meas-
urement can be controlled by the
control system via a digital control
input. To do this,
External
must be
set in the
Scrubber\Scrubber\ Con-
trol
menu and a connection to the
control system must be established.
The control signal has the same
function as the “Measurement
ON/OFF” button. The signal lamp in-
dicates the current state of the con-
trol signal in the control system.
Measurement
ON/OFF
button:
Pressing this button starts the water
circulation. The inlet valve is opened
and the internal circulation is started.
After the maximum tank level has
been reached, the return valve opens
and the return pump starts. To stop
the water circulation, press the but-
ton again.
Loop/Spiking
button: Pressing this button starts the spike mode. This is used for
checking the calibration of the instruments using a calibration solution. Spike
mode activates the internal circulation of the measuring instruments. The sample
supply and return lines are closed. To cancel this mode, press the button again.
Drain tank
button: Pressing and holding this button drains the system. To cancel
this mode, release the button.