SIGALARM INSTALLATION AND OPERATION MANUAL /
GENERATION 4 WIRELESS
16
▶
Apply power to the unit and verify
the LCD screen turns on and
the unit goes into a maximum
status. If no sensors are bonded
“no data” will appear.
▶
Select the reset button and verify
the control module reverts from
max to the last displayed set
point. The set point auto saves
every 10 seconds.
▶
Verify the correct quantities of
sensors installed are showing in
the home screen/ detail view, as
well as the active sensor column
of the manage sensors screen
▶
Using the decrease icon or -
button lower the set point to
initiate a
warning status. Verify
that the external and internal
speakers alarm. Also check that
visual warnings on the control
module are functioning.
▶
If relay options are being
utilized verify they are
functioning properly.
▶
Using the decrease icon or the -
button, lower the set point further
to initiate a
danger status.
▶
Verify that the external and
internal speakers alarm. Also
check that visual warnings on the
control module are functioning.
▶
If relay options are being
utilized verify they are
functioning properly.
▶
Depress the override icon and
adjust the setpoint back to the
desired level.
Verify your installation is correct, and complete the operation
set up prior to operating equipment near power lines.
2.8 TESTING THE INSTALLATION