NIM Primitives
4-7
TIWAY 1 Ti505 NIM User Manual
The subset of TIWAY I Primitives supported by the Series 505 NIM is given in Table 2.
Future additions to this subset will be announced as they are implemented. Note that
each of the following Primitives fits into the general categories listed in Table 1.
Table 2 Series 505 NIM Primitive Subset
Primitive Code (HEX)
Non–extended
Address
Extended
Address
Type
00
80
Exception reporting
01
81
Native
02
82
Attached device / NIM status
03
83
Attached device type/configuration
04
84
Primitive format configuration
05
85
Packed native
10
90
Change state
20
A0
Read block (single contiguous block)
21
A1
Read random block
30
B0
Write block (single contiguous block)
31
B1
Write random block
50
D0
Define blocks (up to 32 separate blocks)
51
D1
Gather defined blocks
52
D2
Write and gather defined blocks
55
D5
Define records (up to 32 records)
56
D6
Gather defined records
57
D7
Write and gather defined records
You can use extended addresses by adding 80hex to the non-extended address primitive.
With extended addresses, the AAAA field is expanded from sixteen bits to 32 bits
(AAAAAAAA). This allows you to access data element locations beyond the non-ex-
tended limit of 65,535. With extended addresses, you can access up to 4,294,967,296 loca-
tions.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com