Primitive Examples
E-2
TIWAY 1 TI505 User Manual
In this example, the same task is performed as in the above example, but with extended
addressing.
Command: LLLL A0 TT NNNN AAAA AAAA = 0008 A0 01 0004 0000 0064, where:
LLLL (Length) = 0008
Primitive Code = A0 (extended address format for Primitive 20)
TT (Data Type) = 01 (V, variable memory)
NNNN (Number of locations) = 0004
AAAA AAAA (Address) = 0000 0064
Response: LLLL A0 HH DD ... DD = 000A A0 00 8464 8665 A001 01F4
LLLL (Length) = 000A
Primitive Code = A0 (extended address format for Primitive 20)
HH (Status) = 00 (unit operational and executing logic)
DDDD ... (values read from V memory)
V100 = 8464
V101 = 8665
V102 = A001
V103 = 01F4
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com