Installation
3-20
TIWAY 1 TI505 NIM User Manual
If the NIM fails the test, the following conditions apply.
1.
If the NIM GOOD LED indicator is extinguished, then an internal NIM failure
was detected.
2.
If the PC GOOD LED indicator is extinguished, then a problem was found in at-
tempting to communicate with a TI505 P/C.
3.
If the XMT LED indicator is extinguished, a failure was detected on the bottom
port (Port B). This could be due to a missing loopback connector.
4.
If the RCV LED indicator is extinguished, a failure was detected on the
top network port (Port A). This could be due to a missing loopback con-
nector.
Following successful execution of the diagnostics, the network cable(s) should be
connected to the NIM, the NIM Reset button should be pressed and the
LOCAL/REMOTE switch should be returned to the correct setting (for your application).
This will reinitialize the NIM, and it will return to normal operation.