Heaters shown in the table provide a maxi-
mum trip rating of 125% of the motor name-
plate amperes, which is suitable for 40°C
motors. For all other motors select heaters
one code number lower than specified in the
table, which
give a maximum trip rating of approximately
115%.
The tripping current of any heater in a 40°C
ambient is 25% greater than the lower value
of motor amperes shown in the table.
Starters do not provide protection from short
circuits. A protective device should be pro-
vided in accordance with the NEC (CEC in
Canada) and not exceed the values shown in
the table.
Note: If the rating specified is not a standard
size for the circuit breaker manufacturer, use
the next largest size.
Hazardous Voltage.
Can cause death or serious
personal injury.
Automatic reset will continue
to reset on two-wire control.
When not desired, use three-
wire control. Do not use manu-
al trip button when relay is set
in automatic reset position.
Siemens Energy & Automation, Inc.
41
E .Standard Trip. Heater Elements for Ambient Temp. Comp. Bimetal Relays
Full Load Heater Max. Rat.
Mo. Amps. Code of Prot.
Min. Max. No. Device*
Size 0 & 1
0.67
0.72
E14
3
0.73
0.80
E16
3
0.81
0.85
E17
3
0.86
0.92
E18
3
0.93
0.99
E19
3
1.00
1.08
E23
3
1.09
1.23
E24
3
1.24
1.37
E26
3
1.38
1.54
E27
3
1.55
1.69
E28
3
1.70
1.80
E29
3
1.81
1.94
E31
3
1.95
2.07
E32
3
2.08
2.26
E33
3
2.27
2.54
E34
7
2.55
2.69
E36
7
2.70
2.88
E37
7
2.89
3.14
E38
7
3.15
3.40
E39
7
3.41
3.81
E41
7
3.82
4.26
E42
7
4.27
4.62
E44
7
4.63
5.09
E46
7
5.10
5.61
E47
7
5.62
5.91
E48
7
5.92
6.15
E49
15
6.16
6.70
E50
15
6.71
7.54
E51
15
7.55
8.29
E52
15
8.30
8.99
E53
15
9.00
9.85
E54
15
9.86
10.4
E55
15
10.5
12.0
E56
15
12.1
13.6
E57
30
Full Load Heater Max. Rat.
Mo. Amps. Code of Prot.
Min. Max. No. Device*
Size 13/4
2.27
2.54
E34
7
2.55
2.69
E36
7
2.70
2.88
E37
7
2.89
3.14
E38
7
3.15
3.40
E39
7
3.41
3.81
E41
7
3.82
4.25
E42
7
4.26
4.62
E44
7
4.63
5.09
E46
7
5.10
5.61
E47
7
5.62
5.91
E48
7
5.92
6.15
E49
15
6.16
6.70
E50
15
6.71
7.54
E51
15
7.55
8.29
E52
15
8.30
8.99
E53
15
9.00
9.85
E54
15
9.86
10.4
E55
15
10.5
12.0
E56
15
12.1
13.6
E57
30
13.7
15.6
E60
30
15.7
17.0
E61
30
17.1
19.4
E62
30
19.5
20.9
E65
30
21.0
22.2
E66
30
22.3
25.3
E67
30
25.4
26.9
E69
50
27.0
30.2
E70
50
30.3
33.3
E72
50
D25556-3
Size 2 & 21/2
10.5
12.0
E56
50
12.1
13.6
E57
50
13.7
15.6
E60
50
15.7
17.1
E61
50
17.2
19.4
E62
50
19.5
20.9
E65
50
21.0
22.2
E66
50
22.3
25.3
E67
50
25.4
26.9
E69
50
27.0
30.2
E70
50
30.3
33.3
E72
50
33.4
35.3
E73
50
35.4
41.5
E74
50
41.6
45.0
E76 1
00
Full Load Heater Max. Rat.
Mo. Amps. Code of Prot.
Min. Max. No. Device*
Size 3 & 31/2
30.0
33.5
E69
100
33.6
36.4
E70
100
36.5
39.6
E71
100
39.7
43.6
E73
100
43.7
46.5
E73A
100
46.6
51.6
E74
100
51.7
54.4
E76
100
54.5
58.0
E77
100
58.1
63.0
E78
100
63.1
67.7
E79
100
67.8
72.4
E80
100
72.5
80.0
E94
100
Full Load Heater Max. Rat.
Mo. Amps. Code of Prot.
Min. Max. No. Device*
Size 41/2 & 5
88.0
98.0
E27
250
98.1
108
E28
250
109
114
E29
250
115
122
E31
250
123
130
E32
250
131
140
E33
250
141
155
E34
250
156
166
E36
250
167
177
E37
250
178
193
E38
400
13.7
15.8
E60
30
15.7
17.0
E61
30
17.1
18.4
E62
30
18.5
19.4
E65
30
19.5
21.3
E66
30
21.4
24.4
E67
30
24.5
25.9
E69
30
26.0
26.0
E70
30
Size 1 only
D25385-7
Size 21/2 only
D26069-5
Size 4
56.9
60.9
E89
150
61.0
63.9
E91
150
64.0
67.7
E92
150
67.8
72.4
E93
150
72.5
77.7
E94
150
77.8
85.9
E96
150
86.0
91.9
E97
150
92.0
96.7
E98
150
96.8
105
E99
150
106
115
E103
150
116
130
E104
150
D36024-2
Size 31/2 only
D26801-3
80.1
88.1
E96
100
88.2
91.5
E97
150
91.6
96.8
E98
150
96.9
99.0
E99
150
99.1
108
E101
150
Size 6
166
195
E27
400
196
217
E28
400
218
229
E29
400
230
245
E31
400
246
261
E32
400
262
281
E33
400
282
311
E34
400
312
331
E36
400
332
355
E37
400
356
387
E38
600
388
419
E39
600
420
467
E41
600
468
500
E42
600
D25665-3
194
209
E39
400
210
233
E41
400
234
248
E42
400
Size 5 only
D25651-5
Wye-delta starters:
If the motor name-
plate shows the full load delta line current
only, divide this value by 1.73 or multiply by
.58 to select the proper heater rating.
*Ratings specified are for instantaneous
trip circuit breakers.
Maximum current rating for thermalmag-
netic circuit breakers is 250% of maximum
heater FLA.
Maximum current rating of fuses is:
a. 150% of maximum heater FLA for
Class R, K, or L (time delay).
b. 250% of maximum heater FLA for
Class K or L (non-time delay).
c. 300% of maximum heater FLA for
Class J (non-time delay).
If the calculated rating is between standard
sizes, the next larger size may be used. Fuse
size may not exceed switch size.