5.6 Disconnect Operating Handle Adjustment
Hazardous voltage.
Will cause death or serious
personal injury.
Disconnect power before working
on this equipment.
In rare circumstances, such as when changing a circuit breaker
or a fusible switch or when a unit is taken apart, it may be
necessary to adjust the disconnect operating handle. (The
Siemens fusible disconnect switch for 30A, 60A, 100A, and
200A ratings does not require adjustment.)
1. Perform all disconnect operating handle adjustments with
the unit removed from the motor control center or in the
“test” position.
2. The adjustable link rod can adjust to increase or decrease its
overall length by rotating the sleeve. By rotating the sleeve
clockwise the length is increased and by rotating it counter
clockwise the length is decreased. A hex nut is provided as
part of the adjustable link rod and is tightened against the
sleeve to prevent it from going out of adjustment. The hex
nut must be loose and sufficiently away from the sleeve to
allow it to rotate during the adjustment of the handle.
Siemens Energy & Automation, Inc.
34
On
Trip
Off
Park
Figure 57
Figure 58