Engineer Programming Via the Keypad
59
Siemens Building Technologies
Fire Safety & Security Products
09.2008
10.4.14 Entry Time
To set the entry time setting:
1.
Scroll to the ENTRY TIME programming
option.
2.
Press SELECT.
3.
Enter the preferred time (XX-XXX sec).
4.
Press SAVE to update the setting.
10.4.15 Exit Time
To set the exit time setting:
1.
Scroll to the EXIT TIME programming option.
2.
Press SELECT.
3.
Enter the preferred time (0-720 min).
4.
Press SAVE to update the setting.
10.4.16 Fullset Bell
To set the fullset bell setting:
1.
Scroll to the FULLSET BELL programming
option.
2.
Press SELECT.
3.
Enter the preferred time (0-10 sec).
4.
Press SAVE to update the setting.
10.4.17 Fullset Strobe
To set the fullset strobe setting:
1.
Scroll to the FULLSET STROBE programming
option.
2.
Press SELECT.
3.
Enter the preferred time (0-10 sec).
4.
Press SAVE to update the setting.
10.4.18 Final Exit
To set the final exit time:
1.
Scroll to the FINAL EXIT programming option.
2.
Press SELECT.
3.
Enter the preferred time (1-45 sec).
4.
Press SAVE to update the setting.