Connecting
5.3 Wiring setups for hazardous area installations
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 01/2014, A5E32221386-AB
33
5.3.3
Non-sparking wiring
①
nameplate
The ATEX certificate listed on the nameplate can be downloaded from our website:
Product page (
Go to: Support > Approvals / Certificates.
●
For wiring requirements follow local regulations.
●
Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X / type 4X
/ NEMA 6, IP67, IP68 locations.
5.3.4
Non-incendive wiring (US/Canada only)
①
nameplate
FM/CSA Class 1, Div 2 connection drawing number 23650673 can be downloaded from our
website:
Product page (
Go to Support > Installation Drawings > Level Measurement > SITRANS LR250.
●
For wiring requirements: follow local regulations.
●
Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X / type 4X
/ NEMA 6, IP67, IP68 locations.
●
Refer to Instructions specific to hazardous area installations (Page 34).