Remote operation
7.1 Operating via SIMATIC PDM
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 01/2014, A5E32221386-AB
79
7.1.5.7
Simulation
Note
The Simulation parameter influences output to the control system.
Two options enable you to test the functioning of the Analog Input Function Blocks or the
functioning of everything between the Transducer Block and Output. For more details see
Analog Input Function Blocks 1 and 2 (Page 225).
Simulate analog input to AIFB1 or AIFB2
Allows you to input a simulated measured value, status, and quality, in order to test the
functioning of an Analog Input Function Block.
1.
Open the menu Device – Simulation, and select the desired function block.
2.
Click on the tab Simulation (Measured value).
3.
Enable simulation, enter a percentage value, set the desired quality and status, and click on
Transfer. See Status Byte (Page 234) for more information on status and quality.