![Siemens SITRANS LR25 Quick Start Manual Download Page 22](http://html.mh-extra.com/html/siemens/sitrans-lr25/sitrans-lr25_quick-start-manual_384664022.webp)
7ML19985XN82
SITRANS LR250 (FF) – QUICK START MANUAL
Page EN-21
mm
mm
m
Eng
lis
h
Wizard Complete
In order to save the Quick Start settings it is necessary to select FINISH to apply
changes.
Press Mode
to return to Measurement mode. The Level Transducer Block (LTB) will now
be operational. To view a measurement reading over the network, one of the Analog Input
Function Blocks (AIFB) will need to be setup and scheduled using a network configuration
software tool.
Communications via Foundation Fieldbus
AMS Device Manager
AMS Device Manager is a software package used to commission and maintain SITRANS
LR250 and other process instruments. Please consult the operating instructions or online help
for details on using AMS Device Manager. (You can find more information at
http://www.emersonprocess.com/AMS/.)
Electronic Device Description (EDD)
Check the product page of our website at: www.siemens.com/LR250, under Downloads, for the
latest version of EDD: SITRANS LR250 FF - Foundation Fieldbus - AMS V9.0.
1)
Check that you have the latest version of the EDD for AMS Device Manager that matches
the firmware revision of your instrument, and if necessary download it from the product
page listed above. Save the files to your computer, and extract the zipped file to an easily
accessed location.
2) Launch AMS Device Manager – Add Device Type, browse to the unzipped EDD file and
select it.
3) The device is shipped with a unique tag, consisting of a manufacturer id and serial
number. The device tag can only be read from the device. It is not necessary to change
the device tag to make the device operational, however if you wish to change it, use AMS
Device Manager.
(continued on next page)
Note:
Wizard Complete is only displayed on the instrument when using the
handheld programmer. This step is not part of the Quick Start Wizard when using
AMS Device Manager.)
Options
BACK, CANCEL, FINISH (Display returns to 1.1 Quick Start Wizard menu
when Quick Start is successfully completed.)
Note: If your application has a tank with obstructions, please see the full manual for details
on using Auto False Echo Suppression.
Notes:
• The following instructions assume that the user is familiar with Foundation Fieldbus.
• You will need the full LR250 FF Operating Instructions manual to acquire the list of
applicable parameters.
Note:
SITRANS LR250 requires the EDD for AMS Device Manager version 9.0.