Troubleshooting
10
10.1
Troubleshooting
The following is list of troubleshooting tips and messages that you may encounter. They
include explanations and, in some cases, a recommended action. If a problem seems
unsolvable, contact your local Siemens Ultrasonic Flow Representative for expert help at
www.automation.siemens.com/partner (
http://www.automation.siemens.com/partner
Table 10- 1 Troubleshooting Tips
Error or Message
Probable Cause
Solution
Memory Full!
Response to an attempt to save site data,
when data memory is full.
Delete an obsolete site or clear Datalogger
memory to make room for the new data.
Memory Corrupted!
Memory read error occurred while
accessing the active site data.
Refer to F4 reset procedure in the Operation
Instructions manual.
Chan Not Setup
Response to an attempt to invoke an
operation that requires a channel to be
enabled.
Enable the channel [Channel Setup - Channel
Enable - Yes]. Note that a channel cannot be
enabled until an "Install" operation is completed.
Clr Active Memory?
Response to pressing the F4 key.
Use the F4 function to restore operation if a severe
event (e.g., a violent power surge) disrupts system
operation.
Clr Saved Data?
[Clr Saved Data?] only appears after
pressing the <Down Arrow> to [Clr Active
Memory?].
Answering Yes to [Clr Saved Data?] will erase ALL
saved data. To invoke in RS-232 serial mode, type
@@@ and then press <ENTER> key.
<EOT>
Response to a request to output Datalogger
data to the printer or the Graphics screen
when no Datalogger data exists or at the
end of a transmitted file.
Set up the Datalogger.
No Sites - Press
<ENTER>
Response while trying to recall/delete a site
setup when no sites are stored.
Create a site.
Security
Response upon changing previously
entered data when security switch is in
[Disable] position or security code has been
entered.
Change switch position to [Enable].
Enter previously set security code.
RTC Error
Component level problem.
Meter requires service. Request RMA.
- - -F- - - Fault Alarm
Loss of signal strength (ALC)
Change of Rx signal location (Beam
Blowing)
Recouple sensors with fresh couplant.
Install sensors in Direct mount mode.
Note: If problem persists call Tech support.
Re-space Index
The measured liquid sonic velocity (Vs) is
more than +/- 25% of the average Vs range.
Assure proper pipe dimensions and/or Liquid
data entries are correct.
Properly enter correct Sensor Size into the
meter [Install Sensor] menu.
Confirm sensor spacing is correct by checking
[Install Sensor] menu spacing parameters.
FUH1010 IP65 NEMA 4X Precision Volume
Operating Instructions, 01/2013, A5E32122003-AA
139
Summary of Contents for SITRANS FUH1010
Page 194: ......
Page 195: ......
Page 196: ......
Page 197: ......
Page 198: ......
Page 199: ......
Page 200: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 204: ......
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ...21614 C 1011NFPS 7 ...
Page 232: ...1011NFPS 7 C 21614 ...
Page 233: ...1011NFPS 7 C 21614 ...
Page 234: ...21614 C 1011NFPS 7 ...
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ...21614 C ...
Page 241: ......
Page 242: ......
Page 243: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 244: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 245: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 246: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......
Page 251: ......
Page 263: ...Index FUH1010 IP65 NEMA 4X Precision Volume 202 Operating Instructions 01 2013 A5E32122003 AA ...