Parameters
SITRANS F M TRANSMAG 2
86
Operating Instructions, 11/2009, A5E00102775-07
4.3
Digit.Output2
1
4.3.1
Function
Assignment of a function to digital output
2
’Split value active’: the active output
indicates a current flow value in the 0 to
’Split value’ range (not effective for
PROFIBUS).
Alarm
•
Alarm, Flow dir. forw.,
•
Flow min, Flow max,
Flow min/max,
•
Total. forw. max,
•
Total. rev. max,
•
Total. net max,
•
Total. net min,
•
Split value active,
•
No function
4.3.2
Signal type
Definition of signal logic for active event
Contact closes
•
Contact closes
•
Contact opens
4.3
Digit.input
2
4.3.1
Function
Assignment of a function to the input:
Measured value=0:
Measured value is set to 0 (affects all
outputs and totalizers)
Totalizer reset: reset+start
Measured value
= 0
•
Meas. val. = 0,
•
Total. forw. reset,
•
Total. rev. reset,
•
Total. net reset,
•
Total. all reset,
•
No function
4.3.2
Signal Type
Definition of signal logic
High-active
•
High-active,
•
Low-active
1)
Parameters apply only to devices with 20 mA/Hart communication and digital output 2 (7ME5034-0xxxx)
2)
Parameters apply only to devices with 20 mA/Hart communication and digital input (7ME5034-2xxxx)
3) Parameters apply only to devices with PROFIBUS communication (7ME5034-1xxxx)
Identification
Table A- 5
Function group Identification parameters
5.1
Funct. Unit
5.1.1
Tag
Tag number
(customer
specific)
Text max.:
•
32 characters 3 /
•
8 characters 1,2
5.1.2
Descriptor
Tag descriptor
(customerspecifi
c)
DN 2...12: l
DN >12: m
3
Text max.
•
32 characters 3
•
16 characters 1,2
5.1.3
Message
Tag message
(customer
specific)
Text max. 32 characters
5.2
Manuf.Ident.
5.2.1
Product type
Transmitter order number
(7ME5034-
xxxxx-xxA0)
5.2.2
Serial number
Transmitter serial number
(N1xxxx-
82xxxxx)
5.2.3
Software Rev.
Software version in the transmitter
(3.x.x)