MAG 8000 & MAG 8000 CT
29
SFIDK.PS.026.D9.02
5. Operation
5.
Operation
5.1.1 Meter operation via
key and display
The meter is designed with a single key and a
symbolic display for optimal dialog.
Display
The display is divided into 3 areas.
Top area with symbols for status information.
Middle area with actual information, and the
bottom area with index for actual information and
the selected menu. Some of the information has
additional information connected and the display
will automatically toggle between the information
(see display overview). After 10 minutes without
pressing the key, the display will time-out and go
back to the default configured operator menu.
Key
There are three different ways the interface key
will respond to being pressed: Briefly pressing
the key for less than 2 seconds will advance the
screen to the next index or menu; pressing the
key for 2 to 5 seconds will enter a menu or
escape the menu selection; pressing the key
for longer than 5 seconds while in the (
−
)
operator menu will activate a reset of the
selected value (e.g., totalizer or call-up function)
indicated by an “r”. A flashing “r” indicates
activation of reset. Under power up can the time
and date be set up and a “A” will indicated a
acceptable value has been selected and will
be stored when flashing.
5.1.2 Display symbols
The status information symbols show the actual
operation of the meter.
The tariff symbol shows the actual accounting
tariff. In the operator menu, the tariff value will
change to “r“ if the information is resetable, like
index “5“ - customer totalizer 3.
The alarm symbol is active when an alarm is
active and independently of the alarm output
configuration.
The empty pipe symbol indicates an empty
pipe condition. To conserve power and prevent
false readings due to exposed measurement
electrodes, flow measurement is disabled until
a full pipe is detected and the symbol has dis-
appeared.
The type of power supply is automatically
detected by the meter. When mains power is
supplied, the plug symbol is shown. When
powered by batteries, the battery symbol is
shown while also indicates remaining battery
capacity - see section 5.2. “Operation menu“
index 1 for more information.
The menu bar icons indicate the actual selected
menu and the related index for the selected
information. The display overview shows rela-
tion between menu, index and information.
Only the (
−
) operator menu has information and
functions that can be reset. Under the power up
function, battery power can be preset to 100%
capacity and time and date can be adjusted - an
“A” in the index shows acceptable values. The
end of each menu index shows possible menu
selections.
Summary of Contents for SITRANS F M MAG 8000
Page 60: ...MAG 8000 MAG 8000 CT 60 SFIDK PS 026 D9 02 10 Approvals and certificates ...
Page 61: ...MAG 8000 MAG 8000 CT 61 SFIDK PS 026 D9 02 10 Approvals and certificates ...
Page 62: ...MAG 8000 MAG 8000 CT 62 SFIDK PS 026 D9 02 10 Approvals and certificates ...
Page 63: ...MAG 8000 MAG 8000 CT 63 SFIDK PS 026 D9 02 10 Approvals and certificates ...