MAG 8000 & MAG 8000 CT
22
SFIDK.PS.026.D9.02
4. Commissioning
FT/PDM Meter
Display Parameter/data type
Factory settings
Data range
number
version view
Fix parameter or meter data that
not
are
changeable
104
All
O5
Reset customer totalizer 3
No
Yes/no
105
All
-
Customer totalizer 3 reset date
PS3 production date and time
year-month-day T
hours:minutes:seconds
106
All
-
Flow rate
0 - 1.25 Qn (Q3)
107
All
-
Actual velocity
0 - 12500
108
All
-
Flowrate percent value
0-125% (Q4)
120
All
-
Actual flow meter status
0
0 to 255, binary presented
with
information 1 for bit 0
1: Totalizer 1 or 2 changed or reset,
2: Tariff setting changed or reset,
3: Tariff register changed or reset,
4: Date - time changed,
5: Alarm have been active,
6: Fault log has been reset,
7: Hardware key has been activated,
8: Meter has been power Up
130
All
-
Menu active
63=all menus active
0 to 63, binary presented
with information
1 for bit 0
1: Operator menu,
2: Meter info menu,
3: Service menu,
4: Log menu,
5: Statistic menu,
6: Revenue menu
131
All
-
Default operator menu index
Totalizer 1
Totalizer 1, Totalizer 2, Actual Flow rate,
Fault codes, Customer Totalizer
200
All
O4
Fault status
0
0 to 8191, binary presented
with
information 1 for bit 0
1: Insulation error,
2: Coil current error,
3: Preamplifier overload,
4: Database checksum error,
5: Low power warning,
6: Flow overload warning,
7: Pulse A overload warning,
8: Pulse B overload warning,
9: Consumption interval warning,
10/L: Leakage warning,
11/E: Empty pipe warning,
12/C: Low impedance (high conductivity)
warning,
13/d: Flow limit warning
201
All
-
Alarm configuration list
254= Alarm 2 to 8 enabled
0 to 8191,
See 200
202
All
-
Date of fault log reset
PS3 production date and time
year-month-day T
hours:minutes:seconds
203
All
O4
Non optimal measure time
0
204
All
-
Reset the fault log and faults
2000-01-01 T 00:00:00
205
All
-
Call up acknowledge
No
Yes/no
206
All
-
Battery alarm level
10%
0-100%
208
All
-
Reset leakage fault
No
Yes / No
209
All
-
Reset consumption log fault
No
Yes / No
210
All
-
Insulation alarm output enable
No
Yes / No
211
All
-
Insulation fault hours
0
212
All
-
Insulation fault counter
0
213
All
-
Insulation fault appears
2000-01-01 T 00:00:00
214
All
-
Insulation fault disappears
2000-01-01 T 00:00:00
215
All
-
Coil current alarm output enable
Yes
Yes / No
216
All
-
Coil current fault hours
0
217
All
-
Coil current fault counter
0
218
All
-
Coil current fault appears
2000-01-01 T 00:00:00
219
All
-
Coil current fault disappears
2000-01-01 T 00:00:00
220
All
-
Amplifier alarm output enable
Yes
Yes / No
221
All
-
Amplifier fault hours
0
222
All
-
Amplifier fault counter
0
Summary of Contents for SITRANS F M MAG 8000
Page 60: ...MAG 8000 MAG 8000 CT 60 SFIDK PS 026 D9 02 10 Approvals and certificates ...
Page 61: ...MAG 8000 MAG 8000 CT 61 SFIDK PS 026 D9 02 10 Approvals and certificates ...
Page 62: ...MAG 8000 MAG 8000 CT 62 SFIDK PS 026 D9 02 10 Approvals and certificates ...
Page 63: ...MAG 8000 MAG 8000 CT 63 SFIDK PS 026 D9 02 10 Approvals and certificates ...