224
43-TV-25-35 GLO Iss.4 Dec 06 UK
A5E01001767-04
Specification Tables
Data Storage
Removable Media:
Compact Flash card supports up to 4.0 Giga bytes. (Compact Flash is not avail-
able as an option for the
D200
)
Local Mass Storage Options:
USB memory key - up to 2Gb, USB hard drive - up to 120Gb,
Internal Data Buffer D300 and D400 Recorder:
Non-volatile. 70MB (16 million acquisition values)
upwards to 1850MB (up to 400 million points)
Internal Data Buffer D200 Recorder:
Non-volatile. 70MB (16 million acquisition values) upwards to
400MB (up to 90 million points)
Setup and screens:
Stored internally on non-volatile memory
Manual Saving:
Data saving by inserting Compact Flash card or USB memory stick
Data Saving Period:
Related to log rate, number of pens, totals and alarms. Each pen is capable of
its own independent storage rate.
D300
and
D400
Recorder:
20ms to 60h,
D200
Recorder: 100mS to 60h.
Data Format:
binary encoded format
Recycling Mode:
Internal memory has FIFO (First In First Out) capability where the newest data
over-writes the oldest data.
Power Requirements
D300 Recorder
Voltage (VRMS):
100VAC to 250VAC (auto select). Frequency: 50/60Hz
Power Consumption:
<40W.
24V Optional instrument power:
20 to 55VDC/20 to 30VAC. Power Consumption: < 40 watts
D400 Recorder
Voltage (VRMS):
100VAC to 250VAC (auto select). Frequency: 50/60Hz
Power Consumption:
<60W.
24V Optional instrument power:
20 to 55VDC/20 to 30VAC. Power Consumption: < 60 watts
D200 Recorder
Voltage (VRMS):
100VAC to 250VAC (auto select). Frequency: 50/60Hz
Power Consumption:
<40W.
24V Optional instrument power
20 to 30VDC/20 to 25VAC. Power Consumption: < 40 watts
Common Relay Output (SPNC)
NC common alarm relay: Two contacts, normally open when the recorder is powered (no active
alarms). Rating 24V, 1 Amp. (Not available for the
D200
)
Battery
Battery backed up for clock, replaceable Lithium battery Type 6032, 3.0V – 10 years life (Recorder
powered),
4 years life, typical (Recorder unpowered).
Password Protection
Multiple Administrator control of password setup and management with four levels of password
protection for – Engineer, Supervisor, Technician, and Operator. Up to 50 different users are avail-
able. Password protection restricts user entry to the recorder set up and specific screens.
Engineer – Highest access to all levels, Supervisor, Technician and Operator.
Supervisor – 2nd highest level including Technician and Operator access
Technician – 3rd level including Operator access
Operator – 4th and lowest level of access.
Languages
English UK & US, French, German, Italian, Spanish, Brazilian, Polish, Hungarian, Slovakian,
Czech, Turkish, Romanian, Russian, Portuguese and Greek.
Temperature Units
°C, °F, °K
Recorder Identification
Status bar: Alternately displays Recorder ID and Recorder Screen Name. Displays Time and Date.
Clock
Accuracy: ±29ppm (±1 minute/month) @ 25°C.
Summer/Winter manual or automatic time adjustment or via communications. SNTP Client and/or
Server included for synchronising over Ethernet.
Alarm Set Points
6 per pen integral “soft” alarm set points easily set by user to announce selected out of limit condi-
tions; user can select if an alarm triggers a change in the screen background colour. Alarm triggers
can be set for Hi, Lo, Deviation (latched or unlatched) for alarm acknowledgement.
Alarm Damping – 1 sec to 24 Hours; Hysteresis - +/- 100% of pen scale
Common relay output: 1A 24V, can be activated on any alarm. (Not available for the
D200)
Data Replay Mode
Data replay facility on chart displays at normal, fast or slow speeds with zoom and cursor.
Specification Design Attributes
Summary of Contents for SIREC D200
Page 2: ......
Page 176: ...170 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Firmware Credit System ...
Page 222: ...216 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 238: ...232 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 258: ...252 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 270: ...264 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 274: ...268 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 Modbus Function Codes ...
Page 284: ...278 43 TV 25 35 GLO Iss 4 Dec 06 UK A5E01001767 04 ...
Page 285: ......