Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
50
Figure 2-4
Logic diagram for 50-2 for phases
If parameter
MANUAL CLOSE
is set to
50-2 instant.
or
50-3 instant.
and manual close detection is
used, a pickup causes instantaneous tripping, even if the element is blocked via binary input. The same applies
to 79AR 50-2 inst.